background image

Operating instructions

D4E146-AA07-02

Translation of the original operating instructions

3.2 Nominal data

Motor

M4E068-CF

Phase

1~

1~

Nominal voltage / VAC

230

230

Frequency / Hz

50

60

Method of obtaining
data

fa

fa

Valid for approval/
standard

CE

CE

Speed (rpm) / min

-1

1000

950

Power consumption / W

100

116

Current draw / A

0.44

0.51

Capacitor / µF

2

2

Capacitor voltage / VDB

450

450

Min. back pressure / Pa

0

0

Min. ambient
temperature / °C

-25

-25

Max. ambient
temperature / °C

50

50

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

3.3 kg

Size

146 mm

Motor size

68

Impeller material

Sheet steel, galvanized

Housing material

Sheet steel, galvanized

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP44; installation- and position-dependent

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H0 - dry environment

Installation position

Any

Condensation
drainage holes

None

Mode

S1

Motor bearing

Ball bearing

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

< 0.75 mA

Motor protection

Thermal overload protector (TOP)
internally connected

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 60335-1; CE

Approval

CCC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

3.4 Mounting data

For screw clearance, see Chapter 3.1 Product drawing

Strength class of
screws

8.8

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

3.5 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

Item no. 11589-5-9970 · ENU · Change 202174 · Approved 2019-03-29 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for D4E146-AA07-02

Page 1: ...and otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the elect...

Page 2: ...coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating dev...

Page 3: ...ing the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer...

Page 4: ...NICAL DATA 3 1 Product drawing All dimensions in mm 1 Cable PVC 4G 0 5 mm 4x splice Item no 11589 5 9970 ENU Change 202174 Approved 2019 03 29 Page 4 11 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74...

Page 5: ...eed loads note that the rotating parts of the device are designed for a maximum of one million load cycles If you have special questions consult ebm papst for support Use the device in accordance with...

Page 6: ...an all pole disconnection switch 4 2 1 Requirements Check whether the information on the nameplate matches the connection data If the motor run capacitor was not installed by ebm papst check whether...

Page 7: ...st connect the PE protective earth Connect the cables according to your application When doing so observe Chapter 4 4 Connection diagram Item no 11589 5 9970 ENU Change 202174 Approved 2019 03 29 Page...

Page 8: ...ctions 4 4 Connection diagram U1 blue Z brown U2 black PE green yellow Item no 11589 5 9970 ENU Change 202174 Approved 2019 03 29 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen...

Page 9: ...n your device Send the device to ebm papst for repair or replacement WARNING Live terminals and connections even with device switched off Electric shock Wait five minutes after disconnecting the volta...

Page 10: ...How often What action Contact protection cover for intactness or damage Visual inspection At least every 6 months Repair or replacement of device Device for damage to blades and housing Visual inspect...

Page 11: ...xternal rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electrical insulating materials on the product in cables and wires...

Reviews: