3.2 Nominal data

Motor

M4E094-IF

Phase

1~

1~

Nominal voltage / VAC

230

230

Frequency / Hz

50

60

Method of obtaining
data

fa

ml

Valid for approval/
standard

-

-

Speed (rpm) / min

-1

1300

1310

Power consumption / W

1020

1320

Current draw / A

4.45

5.75

Capacitor / µF

25

25

Capacitor voltage / VDB

400

450

Capacitor standard

S2 (CE)

S2 (CE)

Min. back pressure / Pa

0

50

Min. ambient
temperature / °C

-40

-40

Max. ambient
temperature / °C

70

55

Starting current / A

8.3

7.5

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

14.8 kg

Size

240 mm

Motor size

94

Impeller material

Sheet steel, galvanized

Housing material

Sheet steel, galvanized

Motor suspension

Motor vibration-damped on both sides

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP10

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H0 - dry environment

Ambient temperature
note

Occasional start-up between -40°C and -
25°C is permissible.
For continuous operation at
temperatures below -25°C (e.g.
refrigeration applications) we recommend
our fan design with special low-
temperature bearings.

Installation position

Any

Condensation
drainage holes

None

Mode

S1

Motor bearing

Ball bearing

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP) with
basic insulation

with cable

Axial

Protection class

I (with customer connection of protective
earth)

Motor capacitor
according to EN 60252-
1 in safety protection
class

S2

Conformity with
standards

EN 60034-1 (2010)

Approval

CCC; EAC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

3.4 Mounting data

Strength class of
screws

8.8

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

For screw clearance, see Chapter 3.1 Product drawing
Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

3.5 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

-40 °C

Item no. 12547-5-9970 · ENU · Change 98149 · Approved 2018-07-24 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for D4E240-BA01-01

Page 1: ...ed by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installati...

Page 2: ...ng installation appropriate shielding measures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire set...

Page 3: ...s Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Reson...

Page 4: ...CAL DATA 3 1 Product drawing All dimensions in mm 1 Cable ETFE AWG18 6x crimped splices Item no 12547 5 9970 ENU Change 98149 Approved 2018 07 24 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D...

Page 5: ...ith customer connection of protective earth Motor capacitor according to EN 60252 1 in safety protection class S2 Conformity with standards EN 60034 1 2010 Approval CCC EAC With regard to cyclic speed...

Page 6: ...nnections CAUTION Voltage The device is a built in component and has no disconnecting switch Only connect the device to circuits that can be switched off with an all pole disconnection switch When wor...

Page 7: ...pter 4 4 Connection diagram 4 3 1 Motor protection CAUTION Voltage The device is a built in component and has no disconnecting switch Connect the device to a suitable tripping unit Only connect the de...

Page 8: ...s 4 4 Connection diagram TOP 2x gray U1 blue Z brown U2 black PE green yellow Item no 12547 5 9970 ENU Change 98149 Approved 2018 07 24 Page 8 10 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mul...

Page 9: ...r device Send the device to ebm papst for repair or replacement WARNING Live terminals and connections even with device switched off Electric shock Wait five minutes after disconnecting the voltage at...

Page 10: ...al regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also to be heeded 5 3 2 Disassembly Disassemb...

Reviews: