Operating instructions

G3G200-GN18-20

Translation of the original operating instructions

3. TECHNICAL DATA

3.1 Product drawing

All measures have the unit mm.

Y

Detail Y

Z

View Z / plug assignment

1

3-pole strip to fit mating connector (not included in standard scope of delivery) Tyco No. 350766-1, female connector Tyco No. 926884-1

1.1

L

1.2

N

1.3

PE

2

5-pole strip to fit mating connector (not included in standard scope of delivery) Molex No. 39-01-4050, female connector Molex No. 39-00-
0059

2.1

+

2.2

Speed monitoring

2.3

0-10 VDC

2.4

PWM input

2.5

-

3

Pressure tap optionally available

Item no. 50363-5-9970 · Revision 68161 · Release 2009-10-09 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for G3G200-GN18-20

Page 1: ...are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device m...

Page 2: ...ive parts Escaping gas may also cause explosions Never open the blower WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You cou...

Page 3: ...he operating instructions Using the device in accordance with the permitted ambient temperature see chapter 3 6 Transport and storage conditions and chapter Only using the device in stationary systems...

Page 4: ...ions In addition all application options that are not listed under proper use Item no 50363 5 9970 Revision 68161 Release 2009 10 09 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfin...

Page 5: ...female connector Tyco No 926884 1 1 1 L 1 2 N 1 3 PE 2 5 pole strip to fit mating connector not included in standard scope of delivery Molex No 39 01 4050 female connector Molex No 39 00 0059 2 1 2 2...

Page 6: ...ion any Condensate discharge holes Rotor side Operation mode S1 Motor bearing Ball bearing Technical features Tach output Over temperature protected electronics motor PFC active Motor current limit Li...

Page 7: ...trical voltage The device is a built in component and features no electrically isolating switch Connect the device only to circuits that can be switched off using an all pole disconnecting switch When...

Page 8: ...n Due to the locked rotor protection the start up current LRA is equal to or less than the nominal current FLA Item no 50363 5 9970 Revision 68161 Release 2009 10 09 Page 8 12 ebm papst Mulfingen GmbH...

Page 9: ...e 16 45 VDC residual ripple 3 5 SELV ST2 2 Tach Speed monitoring 3 pulses per revolution SELV ST2 3 0 10 V Control input 0 10 V impedance 100k SELV ST2 4 PWM Control input PWM 1 6 kHz SELV ST2 5 GND G...

Page 10: ...device Switching off the device during operation Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for ma...

Page 11: ...if imbalance is still evident after cleaning replace the device If you have attached any weight clips during cleaning make sure to remove them afterwards Motor does not turn Mechanical blockage Switc...

Page 12: ...Visual inspection At least every 6 months Replace wires Condensate discharge holes for clogging as necessary Visual inspection At least every 6 months Open bore holes Check the ball bearings to ensure...