Operating instructions

G3G225-DD29-74

Translation of the original operating instructions

4.2.2 Idle current

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and interference immunity), idle
currents in the mains cable can be measured even when the
motor is at a standstill and the mains voltage is switched on.

The values are typically in the range < 250 mA

At the same time, the effective power in this operating state
(operational readiness) is typically < 4 W.

4.2.3 Residual current operated device

If the use of a residual current device (RCD) is required in your
installation, only pulse current-sensitive and/or universal
residual current devices (type A or B) are permissible.
Residual current devices (RCD) cannot provide personal safety
while operating the device, as is also the case with frequency
converters. When the device power supply is switched on,
charging current pulses from the capacitors in the integrated
EMC filter can lead to the instant triggering of residual current
devices. We recommend residual current circuit breakers
(RCCB) with an activation threshold of 300 mA and delayed
tripping (super-resistant, characteristic K).

4.2.4 Basic insulation of the alarm relay

As the alarm relay only has basic insulation (for TN/TT
systems) and function insulation (for systems with external
conductor earthing) with respect to the mains voltage, and not
double insulation like the rest of the interface, corresponding
precautions must be taken for industrial applications (EN 61800-
5-1).
→ The voltage switched by the alarm relay (e.g. 24 VDC)

must then have no electrical connection to the 10 V output, 0-
10 V control input and GND (electrically isolated interface).

4.2.5 Locked-rotor protection

Due to the locked-rotor protection, the start-up current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connection of the cables

External leads are brought out of device.

;

First connect the "PE" (protective earth) connection.

Connect the lines according to your application. When doing so,
observe chapter 4.4 Connection screen.

Item no. 56041-5-9970 · ENG · Revision 213957 · Release 2020-07-14 · Page 7 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for G3G225-DD29-74

Page 1: ...ts are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device The local industrial safety regulations must always be observed when working on the device Keep the workplace clean and tidy Untidines...

Page 2: ...n installations on the customer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair dangling items of clothing j...

Page 3: ... and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system to the fan Operation in medical equipment with a life sustaining or lifesaving function Moving solids content in flow medium Painting the device Connections e g screws coming loo...

Page 4: ...e halogen free railway application EN 45545 5G 1 0 mm 5x core end sleeve 2 Connection line halogen free railway application EN 45545 3x 0 33 mm 3x core end sleeve Item no 56041 5 9970 ENG Revision 213957 Release 2020 07 14 Page 4 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...rial of impeller Sheet steel galvanised Housing material Sheet steel galvanised Direction of rotation Counter clockwise seen on rotor Type of protection IP54 Insulation class B Humidity F environmental protection class H H1 Mounting position Any Condensation drainage holes None Operation mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 1 1 mA Alarm relay Motor current limit ...

Page 6: ...ad 50 µC between mains wire and protective earth connection after switching of the supply when switching multiple devices in parallel Electric shock risk of injury Make sure that sufficient protection against accidental contact is provided Before working on the electrical connection the connections to the mains supply and PE must be shorted CAUTION Electrical voltage The device is a built in compo...

Page 7: ...ecommend residual current circuit breakers RCCB with an activation threshold of 300 mA and delayed tripping super resistant characteristic K 4 2 4 Basic insulation of the alarm relay As the alarm relay only has basic insulation for TN TT systems and function insulation for systems with external conductor earthing with respect to the mains voltage and not double insulation like the rest of the inte...

Page 8: ...ginal operating instructions 4 4 Connection screen Item no 56041 5 9970 ENG Revision 213957 Release 2020 07 14 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 9: ...be sure to disconnect the earth wire connection last 5 INTEGRATED PROTECTIVE FUNCTIONS The integrated protective functions cause the motor to switch off automatically in case of faults described in the table Malfunctions Description Function of safety feature Rotor position detection error An automatic restart occurs Locked rotor After the blockage is removed the motor restarts automatically Line ...

Page 10: ...asedcleaning agents Do not use any pointed or sharp edged objects for cleaning Completely remove any cleaning agents used Immediately switch off and replace the device if severe corrosion is apparent at load bearing or rotating parts Repairs to load bearing or rotating parts are not permissible Operate the fan for 2 hours at maximum speed to permit the evaporation of any water which may have ingre...

Page 11: ...nts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 3 3 Component disposal The products are mostly made of steel copper aluminium and plastic Metallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron...

Reviews: