background image

Operating instructions

G3G250-MW50-01

Translation of the original operating instructions

You can control the blower either via the 0-10 VDC input or the
PWM input. Note: Inputs cannot be used simultaneously.

3.2 Nominal data

Motor

M3G112-EA

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Type of data definition

ml

Speed (rpm) / min

-1

6100

Power input / W

2400

Current draw / A

4.0

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

50

Min. temp. of flow
medium / °C

-25

Max. temp. of flow
medium / °C

+50

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data in accordance with ecodesign regulation EU 327/
2011

Actual

Request 2015

01 Overall efficiency η

es

/ %

59.8

54.3

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

66.5

61

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
rating plate on the product.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
County court Stuttgart · HRA 590344
D-74673 Mulfingen

08 Type

G3G250-MW50-01

09 Power input P

ed

/ kW

2.29

09 Air flow q

v

/ m³/h

1165

09 Pressure increase total p

sf

/

Pa

4000

10 Speed (rpm) n / min

-1

6495

11 Specific ratio

*

1.04

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data definition with optimum efficiency. The ErP data is determined using a motor-impeller

combination in a standardised measurement configuration.

3.4 Technical features

Mass

22.3 kg

Size

250 mm

Motor size

112

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium

Material of impeller

Aluminium sheet

Housing material

Die-cast aluminium

Material of distancing
profiles

Aluminium

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP20

Insulation class

"B"

Humidity (F) /
environmental
protection class (H)

H1

Mounting position

Any

Cooling bore / aperture

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Tach output
- Alarm relay
- Motor current limit
- PFC, passive
- Soft start
- Control input 0-10 VDC / PWM
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical connection

Terminal box

Motor protection

Thermal overload protector (TOP) wired
internally

Protection class

I (if protective earth is connected by
customer)

Approval

UL 1004-7 + 60730-1; EAC

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

;

Use the device in accordance with its protection type.

Notes on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may vary during the production period.
Strength, dimensional stability and dimensional accuracy are not affected
by this.
The colour pigments of the paints used react perceptibly to UV light over
the course of time. This does not however have any influence on the
technical properties of the products. To prevent the formation of patches
and fading, the product is to be protected against UV radiation. Changes
in colour are not a reason for complaint and are not covered by the
warranty.

Item no. 50734-5-9970 · ENG · Revision 202174 · Release 2018-12-28 · Page 6 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for G3G250-MW50-01

Page 1: ...rry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device The local industrial safety regulations must always be observed when working on the device Keep the workplace clean and tidy Untidiness in the working area increases the risk of ...

Page 2: ...alled appropriate shielding measures have to be taken by the user NOTE Electrical or electromagnetic interferences after integrating the device in installations on the customer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Danger of injury from open blower Gas escapes When the blower is open you come into contact with rotating and electrically live parts Escap...

Page 3: ... TN TT power systems only The device is to be used in networks with network quality characteristics as per EN 50160 Moving air in gas burners Conveying of air at an ambient air pressure of 750 mbar to 1050 mbar Minding the operating instructions Using the device within the permitted ambient temperature range see chapter 3 6 Transport and storage conditions and chapter 3 2 Nominal data Only using t...

Page 4: ...use Operation in medical equipment with a life sustaining or lifesaving function Moving solids content in flow medium Painting the device Connections e g screws coming loose during operation Opening the terminal box during operation Item no 50734 5 9970 ENG Revision 202174 Release 2018 12 28 Page 4 15 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 8...

Page 5: ...1 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 2 Depth of screw 10 12 mm tightening torque 20 3 Nm 3 Tightening torque 3 5 0 5 Nm Item no 50734 5 9970 ENG Revision 202174 Release 2018 12 28 Page 5 15 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 6: ...50 mm Motor size 112 Surface of rotor Coated in black Material of electronics housing Die cast aluminium Material of impeller Aluminium sheet Housing material Die cast aluminium Material of distancing profiles Aluminium Direction of rotation Clockwise seen on rotor Type of protection IP20 Insulation class B Humidity F environmental protection class H H1 Mounting position Any Cooling bore aperture ...

Page 7: ... rotating parts do not scrape against stationary parts DANGER Leaks may occur As a result of design necessities the gas blower is not tightly sealed e g at the shaft opening This may cause leaks during operation Deflagrations may also cause long term damage or deformation of the housing which can result in leaks An air gas mixture may accumulate outside of the gas blower The blower may explode You...

Page 8: ... voltage matches the operating voltage of the device Only use cables designed for current according to the type plate For determining the cross section follow the basic principles in accordance with EN 61800 5 1 The protective earth must have a cross section equal to or greater than the outer conductor cross section We recommend the use of 105 C cables Ensure that the minimum cable cross section i...

Page 9: ...laces where cables are inserted Mount the screwed cable glands with the seal inserts provided in the terminal box Insert the line s not included in the standard scope of delivery into the terminal box First connect the PE protective earth connection Connect the lines to the corresponding terminals Use a screwdriver to do so During the connection work ensure that no cables splice off Fig 2 Connecti...

Page 10: ... Control mode parameter set 2 PWM controlling Fan device adress 01 Max PWM 100 Min PWM 5 1 Save set value to EEPROM Yes Set value control Analogue linear Control function parameter set 1 Positive heating Control function parameter set 2 Positive heating Item no 50734 5 9970 ENG Revision 202174 Release 2018 12 28 Page 10 15 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 793...

Page 11: ...ground for control interface 3 GND GND Signal ground for control interface 3 0 10 V 0 10 V Analogue setpoint input 0 10 V impedance 100 kΩ can be used exclusively as an alternative to connection PWM for correct function the PWM input must be bridged with GND 3 20 V 20 V Supply for external sensor 20 VDC 20 max 50 mA 3 10 V 10 V Supply for external potentiometer 10 VDC 10 max 10 mA 3 Tach Tach Spee...

Page 12: ... must operate free of vibrations throughout its speed control range Strong vibrations can result from improper handling imbalance resulting from damage during transport or component induced or structural resonances When putting the fan into service determine the speed ranges with excessive vibration levels and also any resonance frequencies that may be present When regulating the speed pass throug...

Page 13: ...ning roughly Imbalance in rotating parts Clean the device if imbalance is still evident after cleaning replace the device If you have attached any weight clips during cleaning make sure to remove them afterwards Motor does not turn Mechanical blockage Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The erro...

Page 14: ...ISO 14001 and rigorously implemented around the world on the basis of German standards Right from the development stage ecological design technical safety and health protection are fixed criteria The following section contains recommendations for ecological disposal of the product and its components 6 3 1 Country specific legal requirements NOTE Country specific legal requirements Always observe t...

Page 15: ...pose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 50734 5 9970 ENG Revision 202174 Release 2018 12 28 Page 15 15 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Reviews: