K3G400-PA27-W4

Translation of the original operating instructions

H = max

. 5

L  H x 

Assembled FanGrids may not be transported.
There is a risk that the assembly could fall over or be damaged.
If it is not possible to mount the fan combination to the floor, wall and ceiling, the fan combination must be mounted in an auxiliary
construction that is suitably stable.
The construction in which the fans are mounted must have sufficient strength to bear any loads that may occur over the entire service life.
In order to avoid heavy loads due to the composite bending, from a height of four fans and a width of six fans, a consistent, vertical strut
must be installed approximately in the center.
From a width of nine fans, a corresponding number of additional vertical struts must be installed. The struts can be attached both on the
intake side and the outlet side.
The casing between the fans and the wall or ceiling (as a bulkhead) must not be used as a supporting element.

Item no. 56983-5-9970 · ENU · Change 254197 · Approved 2022-05-23 · Page 6 / 20

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for K3G400-PA27-W4

Page 1: ...test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation...

Page 2: ...ore working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and caus...

Page 3: ...6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device i...

Page 4: ...Nm The tightening torque is designed for PVC cables If the cable materials are different the tightening torque may have to be adjusted 3 Tightening torque 1 5 0 2 Nm 4 Inlet ring with pressure tap k...

Page 5: ...fans Use M8 or 8 mm diameter screws and if necessary screw anchors of sufficient size and strength that the fan assembly cannot come loose even under heavy load Maximum height 5 FanGrid fans vertical...

Page 6: ...the entire service life In order to avoid heavy loads due to the composite bending from a height of four fans and a width of six fans a consistent vertical strut must be installed approximately in the...

Page 7: ...duction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019...

Page 8: ...for professionally used equipment with a total rated power greater than 1 kW If several devices are connected in parallel on the supply side so that the line current of the arrangement is in the range...

Page 9: ...ons CAUTION Voltage The fan is a built in component and has no disconnecting switch Only connect the fan to circuits that can be switched off with an all pole disconnection switch When working on the...

Page 10: ...esidual current circuit breakers RCCB with a trip threshold of 300 mA and delayed tripping super resistant characteristic K 4 2 5 Leakage current For asymmetrical power systems or if a phase fails the...

Page 11: ...cable diameter the seals included in the terminal box must be inserted into the cable gland if necessary Route the cable s not included in the scope of delivery into the terminal box Ensure separate r...

Page 12: ...ble a drip edge can be produced by fitting a cable tie directly in front of the cable gland for example 4 4 Factory settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM...

Page 13: ...eristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Fan modulation level Characteristic curve param...

Page 14: ...159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k 10KHz SELV Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 active...

Page 15: ...operating instructions 4 7 Equivalent circuit diagrams Item no 56983 5 9970 ENU Change 254197 Approved 2022 05 23 Page 15 20 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 793...

Page 16: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Page 17: ...automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Inadequate cooling Improve cooling Allow the device to...

Page 18: ...nsors depends on the device concerned and the installation situation 6 3 Cleaning To ensure a long service life check the fans regularly for proper operation and soiling The frequency of checking is t...

Page 19: ...on the basis of German standards Right from the development stage ecological design technical safety and health protection are fixed criteria The following section contains recommendations for ecolog...

Page 20: ...ploying the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 56983 5 9970 ENU Change 254197 Approved 2022 05 23 Page 20 20 ebm papst Mulfinge...

Reviews: