background image

Operating instructions

K3G450-RS04-G2

Translation of the original operating instructions

4.5 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Color

Function/assignment

1

1, 2

PE

green/
yellow

Protective earth

1

3

N

blue

Power supply, neutral conductor, 50/60 Hz

1

5

L

black

Power supply, phase, 50/60 Hz

1

6

NC

white 1

Status relay, floating status contact; break for failure, contact rating 250 VAC / 2A (AC1) / min. 10
mA, basic insulation on supply side and reinforced insulation on control interface side

1

7

COM

white 2

Status relay, floating status contact; common connection, contact rating 250 VAC / 2A (AC1) / min.
10 mA, basic insulation on supply side and reinforced insulation on control interface side

2

8

0-10V

yellow

Analog input (set value); 0-10 V; Ri = 100 kΩ; adjustable curve

2

10

RSB

brown

RS485 interface for MODBUS, RSB

2

11

RSA

white

RS485 interface for MODBUS, RSA

2

12

GND

blue

Reference ground for control interface, SELV

2

13

+10V

red

Fixed voltage output 10 VDC, +10 V ±3%; max. 10 mA; short-circuit-proof; power supply for
external devices (e.g. pot)

Item no. 52832-5-9970 · ENU · Change 211950 · Approved 2020-09-21 · Page 9 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for K3G450-RS04-G2

Page 1: ...zed specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associ...

Page 2: ...ntact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and...

Page 3: ...pter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and coul...

Page 4: ...drawing All dimensions in mm 1 Cable PVC AWG18 5x crimped ferrules 2 Cable PVC AWG22 5x crimped ferrules Item no 52832 5 9970 ENU Change 211950 Approved 2020 09 21 Page 4 13 ebm papst Mulfingen GmbH...

Page 5: ...Data obtained at optimum efficiency level The ErP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 16 7 kg Size 450 mm Motor s...

Page 6: ...Never subject to any impact Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when unpacking device Risk of physical injury such as back injuries Two people should work together to...

Page 7: ...use of the EMC filter integrated for compliance with EMC limits interference emission and immunity to interference reactive currents can be measured in the supply line even when the motor is at a stan...

Page 8: ...d be routed in a U shaped loop wherever possible If this is not possible a drip edge can be produced by fitting a cable tie directly in front of the cable gland for example When routing the cable make...

Page 9: ...relay floating status contact common connection contact rating 250 VAC 2A AC1 min 10 mA basic insulation on supply side and reinforced insulation on control interface side 2 8 0 10V yellow Analog inpu...

Page 10: ...ossibly resonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with...

Page 11: ...am Motor electronics overtemperature Deficient cooling Improve cooling Let the device cool down To reset the error message switch off the line voltage for at least 25 s and then switch it on again The...

Page 12: ...st every 6 months Open holes Abnormal bearing noise acoustic At least every 6 months Replace device Vibration test Vibration tester start up or deceleration measurement Recommended every 6 months Clea...

Page 13: ...s Miscellaneous insulators used in the terminal box Power cables Cables for internal wiring Electrolytic capacitors Dispose of electronic components employing the proper procedures for electronic scra...