3.2 Nominal data

Motor

M3G150-IF

Phase

3~

Nominal voltage / VAC

200

Nominal voltage
range / VAC

200 .. 240

Frequency / Hz

50/60

Type of data definition

ml

Speed / min

-1

1510

Power input / W

2900

Current draw / A

9.2

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

45

ml = max. load · me = max. efficiency · fa = running at free air

cs = customer specs · cu = customer unit

Subject to alterations

3.3 Technical features

Mass

43 kg

Size

560 mm

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium

Material of impeller

Aluminium sheet

Material of mounting
plate

Sheet steel, hot-dip galvanised

Material of distancing
profiles

Aluminium

Material of inlet nozzle

Sheet steel, hot-dip galvanised

Number of blades

9

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F4-1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- PFC, passive
- Control input 0-10 VDC / PWM
- Over-temperature protected
electronics / motor
- Alarm relay
- Integrated PID controller
- Input for sensor 0-10 V or 4-20 mA
- Output for slave 0-10 V
- RS485 ebmBUS
- Motor current limit
- Soft start
- Line undervoltage / phase failure
detection
- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Reverse polarity and locked-rotor
protection

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

GOST; UL 2111; CSA C22.2 Nr.77

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.4 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.5 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

3.6 Electromagnetic compatibility

If several devices are switched in parallel on the mains side so
that the line current of the arrangement is in the range of 16 - 75
A, then this arrangement conforms to IEC 61000-3-12 provided
that the short-circuit power S

sc

at the connection point of the

customer system to the public power system is greater than or
equal to 120 times the rated output of the arrangement.
It is the responsibility of the installation engineer or operator/
owner of the device to ensure, if necessary after consultation
with the network operator, that this device is only connected to
a connection point with a S

sc

value that is greater than or equal

to 120 times the rated output of the arrangement.

Item no. 50418-5-9970 · Revision 68161 · Release 2010-08-05 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for K3G560-AH07-13

Page 1: ...transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evalua...

Page 2: ...g on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing...

Page 3: ...imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids content in flow medium Pai...

Page 4: ...l measures have the unit mm 1 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 2 Tightening torque 3 5 0 5 Nm Item no 50418 5 9970 Revision 68161 Release 2010 08 05 Page 4 12 ebm papst Mul...

Page 5: ...on Reverse polarity and locked rotor protection Protection class I if protective earth is connected by customer Product conforming to standard EN 61800 5 1 CE Approval GOST UL 2111 CSA C22 2 Nr 77 For...

Page 6: ...nters at the cable end on the customers side and can damage the device Make sure that the cable end is connected in a dry environment Connect the device only to circuits that can be switched off using...

Page 7: ...r 3 1 Product drawing Ill 1 Recommended stripping lengths in mm inside the terminal box 4 3 2 Connecting cables with terminals WARNING Terminals and connections have voltage even with a unit that is s...

Page 8: ...tion mode PWM controlling Group adress 1 Fan device adress 1 Max PWM 100 Min PWM 0 Save set value to EEPROM Yes Set value control Analog Control function Positive heating Item no 50418 5 9970 Revision...

Page 9: ...te to 100 level control coefficient KL3 2 8 GND Reference mass for control interface SELV KL3 3 7 0 10 V Use control actual value input 0 10 VDC impedance 100 k only as alternative to 4 20 mA input SE...

Page 10: ...ng off the device during operation Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work...

Page 11: ...ght clips during cleaning make sure to remove them afterwards Motor does not turn Mechanical blockage Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supp...

Page 12: ...y 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visua...

Reviews: