background image

Operating instructions

K3G710-PV05-02

Translation of the original operating instructions

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
In the event of a fault, the rotor and the impeller will be
energized

The rotor and the impeller have basic insulation.
→ Do not touch the rotor and impeller once installed.

CAUTION
If control voltage or a stored speed set value is applied,
the motor will restart automatically, e.g. after a power
failure.

Risk of injury
→ Keep out of the device’s danger zone.
→ When working on the device, switch off the line voltage

and ensure that it cannot be switched back on.

→ Wait until the device comes to a stop.
→ After working on the device, remove any tools or other

objects from the device.

1.5 Safety and protective features

DANGER
Guard missing and guard not functioning

Without a guard, hands may become caught up in the device
during operation for example, resulting in serious injury. Loose
parts or items of clothing could be drawn in.
→ The device is a built-in component. As the owner, you are

responsible for ensuring that the device is adequately
safeguarded.# Operate the device only with a fixed
protective device and guard grill.

→ Stop the device immediately if a protective device is

found to be missing or ineffective.

1.6 Electromagnetic radiation

NOTE
Electrical or electromagnetic interference after installing
the device in customer equipment.

→ Verify that the entire setup is EMC-compliant.

1.7 Mechanical movement

DANGER
Rotating device

Risk of injury to body parts coming into contact with the rotor or
the impeller.
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all

parts have come to a standstill.

DANGER
Ejected parts

Missing protective devices may cause balancing weights or
broken fan blades to be ejected and cause injuries.
→ Take appropriate safety measures.

WARNING
Rotating device

Long hair and dangling items of clothing, jewelry and the like
can become entangled and be pulled into the device. Injuries
can result.
→ Do not wear any loose-fitting or dangling clothing or jewelry

while working on rotating parts.

→ Protect long hair with a cap.

1.8 Emissions

WARNING
Depending on the installation and operating conditions,
the sound pressure level may exceed 70 dB(A).

Risk of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety

equipment such as hearing protection.

→ Also observe the requirements of local agencies.

1.9 Hot surface

CAUTION
High temperature on electronics housing

Risk of burns
→ Ensure sufficient protection against accidental contact.

1.10 Transport

WARNING
Transporting the fan

Injuries from tipping or slipping
→ The fan is always to be transported with care and in its

original packaging.

→ If set down too hard or at an angle for example, the

impact can lead to bearing damage or deformation of the
frame or impeller.

→ It must be ensured that the fans cannot tip over during

transportation and handling.

→ Secure the fan(s) with appropriate equipment such as a

lashing strip so that nothing can slip or tip, especially when
stacking multiple fans.

→ Also make allowance for possible wind forces.

1.11 Storage

WARNING
Storing the fan

Injuries from tipping or slipping
→ The fans must always be stored and handled so that they

cannot tip over.

→ Secure the fan(s) with appropriate equipment such as a

lashing strip so that nothing can slip or tip, especially when
stacking multiple fans.

→ Also take possible wind forces into consideration.

Item no. 55980-5-9970 · ENU · Change 212420 · Approved 2020-02-17 · Page 2 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for K3G710-PV05-02

Page 1: ...permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devic...

Page 2: ...GER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and cause injuries Take appropriate safety measures WARNING Rotating device Long hair and da...

Page 3: ...forming all maintenance work Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter 3 6 Transport and stora...

Page 4: ...ghtening torque 6 0 9 Nm 5 Tightening torque 3 5 0 5 Nm 6 Attachment holes for FlowGrid 50710 2 2957 not included in scope of delivery 7 Motor support plate Installation position shaft horizontal moto...

Page 5: ...ription Weight 120 7 kg Size 710 mm Motor size 200 Rotor surface Painted black Electronics housing material Die cast aluminum painted black Impeller material Sheet aluminum painted black Support plate...

Page 6: ...t of the arrangement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only...

Page 7: ...re working on the electrical hookup short the supply and PE connections CAUTION Voltage The fan is a built in component and has no disconnecting switch Only connect the fan to circuits that can be swi...

Page 8: ...se of residual current circuit breakers RCCB with a trip threshold of 300 mA and delayed tripping super resistant characteristic K 4 2 5 Leakage current For asymmetrical power systems or if a phase fa...

Page 9: ...possible If this is not possible a drip edge can be produced by fitting a cable tie directly in front of the cable gland for example 4 4 Factory settings Factory settings made for the device by ebm p...

Page 10: ...tact changeover contact common connection contact rating 250 VAC max 2 A AC1 min 10 mA KL2 3 NC Status relay floating status contact break for failure KL 3 1 RSA Bus connection RS485 RSA MODBUS RTU SE...

Page 11: ...PROM setting the integrated controller s direction of action can be selected via bus or digital input Din3 normal pin open or applied voltage 5 50 VDC inverse bridge to GND or applied voltage 1 VDC SE...

Page 12: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Page 13: ...e from supply and remove mechanical blockage Line voltage faulty Check line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning...

Page 14: ...aintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing volta...

Page 15: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...