background image

Operating instructions

R3G190-AF50-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G074-BF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50

Type of data definition

fa

Speed / min

-1

3900

Power input / W

135

Current draw / A

1.0

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = max. load · me = max. efficiency · fa = running at free air

cs = customer specs · cu = customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

40.2

38.5

42.5

Efficiency grade N

59.7

58

62

Power input P

ed

/ kW

0.14

Air flow q

v

/ m³/h

455

Pressure increase total p

sf

/ Pa

418

Speed n / min

-1

3840

Data established at point of optimum efficiency

3.4 Technical features

Mass

1.8 kg

Size

190 mm

Surface of rotor

Galvanised

Material of impeller

Plastic PA66, fibreglass-reinforced

Number of blades

7

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 44; Depending on installation and
position

Insulation class

"B"

Humidity class

F3-1

Mounting position

Any

Condensate discharge
holes

None

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Motor current limit
- Soft start
- Control input 0-10 VDC / PWM
- Over-temperature protected
electronics / motor

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP) wired
internally

Cable exit

Variable

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 60335-1; CE

Approval

UL 507; CSA C22.2 Nr.113

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

For depth of screw, see chapter 3.1 Product drawing

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

3.7 Electromagnetic compatibility

EMC interference
immunity

Acc. to EN 61000-6-2

EMC harmonics

Acc. to EN 61000-3-2/3

EMC interference
emission

Acc. to EN 61000-6-3 (household
environment)

Item no. 51069-5-9970 · Revision 72864 · Release 2011-02-18 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for R3G190-AF50-01

Page 1: ...sonnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the d...

Page 2: ...ire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Befo...

Page 3: ...the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highl...

Page 4: ...blue 1 3 PE green yellow 2 1 Tach output white 2 2 GND blue 2 3 10V red 2 4 0 10V yellow 3 Depth of screw min 8 mm max 10 mm 4 Pilot hole prepared for self tapping screw M4 depth of screw max 6 mm 5...

Page 5: ...chnical features Motor current limit Soft start Control input 0 10 VDC PWM Over temperature protected electronics motor Touch current acc IEC 60990 measuring network Fig 4 TN system 3 5 mA Motor prote...

Page 6: ...ssible Maintain a distance to the power supply line when routing the control lines of the device Ensure a sufficiently large clearance Recommendation clearance 10 cm separate cable routing NOTE Water...

Page 7: ...8 0 10 V PWM yellow Control input 0 10 V or PWM electrically isolated 9 Tach white Tach output open collector 1 pulse per revolution electrically isolated 11 10V max 1 1 mA red Voltage output 10 V ma...

Page 8: ...on Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work Switch on the device via the con...

Page 9: ...tector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device...

Page 10: ...ge Visual inspection At least every 6 months Clean or replace impeller Check the ball bearings to ensure they are quiet can move easily and are free of play Manual check by turning the rotor in shut o...

Page 11: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information ebm papst R3G190 AF50 01...

Reviews: