3.2 Nominal data

Motor

M3G084-GF

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

2650

Power consumption / W

740

Current draw / A

1.4

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to ErP Directive

Actual

Req. 2015

01 Overall efficiency η

es

/ %

66.2

50

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

78.2

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart
· HRA 590344
D-74673 Mulfingen

08 Type

R3G310-RQ10-C6

09 Power consumption P

ed

/ kW

0.72

09 Air flow q

v

/ m³/h

2110

09 Pressure increase total p

sf

/

Pa

747

10 Speed (rpm) n / min

-1

2655

11 Specific ratio

*

1.01

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

6.5 kg

Fan size

310 mm

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum

Impeller material

PP plastic

Number of blades

6

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

F3-1

Installation position

Shaft horizontal or rotor on top; rotor on
bottom on request

Condensation
drainage holes

None

Mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (parameter setting)
- Alarm relay
- Integrated PID controller
- Motor current limitation
- PFC, passive
- RS-485 MODBUS-RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from supply
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Via terminal box

Motor protection

Thermal overload protector (TOP)
internally connected

Protection class

I (if protective earth is connected by
customer to the housing's connection point)

Conformity with
standards

EN 61800-5-1; CE

Approval

UL 1004-7 + 60730; C22.2 No.77 +
CAN/CSA-E60730-1

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

Item no. 52000-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Summary of Contents for R3G310-RQ10-C6

Page 1: ...lified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safet...

Page 2: ...after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the...

Page 3: ...g the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt depo...

Page 4: ...rance for screw 16 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 4 Tightening torque 3 5 0 5 Nm Item no 52000 5 9970 ENU Change 89187 Approved 2016 04 15 Page 4 12 ebm papst Mulf...

Page 5: ...Weight 6 5 kg Fan size 310 mm Rotor surface Painted black Electronics housing material Die cast aluminum Impeller material PP plastic Number of blades 6 Direction of rotation Clockwise viewed toward...

Page 6: ...ot to be installed Install the undamaged device in accordance with your application CAUTION Possible damage to the device If the device slips during installation serious damage can result Ensure that...

Page 7: ...ker RCCB Only universal residual current devices type B or B are allowed As with variable frequency drives residual current devices cannot provide personal safety while operating the device When the d...

Page 8: ...ter set 1 PWM control Mode parameter set 2 PWM control Fan device address 1 Max PWM 100 Min PWM 5 1 Save set value to EEPROM Yes Set value requirement Analog linear Direction of action parameter set 1...

Page 9: ...ensor value input 0 10 VDC impedance 100 k only as alternative to 4 20 mA input SELV KL3 4 10 V Voltage output 10 VDC 3 max 10 mA power supply for external devices e g potentiometer SELV KL3 5 20 V Vo...

Page 10: ...ture description function Rotor position detection error An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically Line undervoltage line voltage outsid...

Page 11: ...The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing voltage is applied Test the device with DC voltage when you perform the legally required high voltage test...

Page 12: ...Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Only f...

Reviews: