background image

Operating instructions

R3G500-DA25-05

Translation of the original operating instructions

;

Connect the cables to the corresponding terminals. Use a
screwdriver to do so. When connecting, make sure the wires do not
splay out. Insert the strands until they meet with resistance.

Fig. 4: Connection of cables at terminals

;

There must not be any tensile stress between the terminal and the
cable gland. The cable must be provided with strain relief.

;

The cable glands must be tight.

;

Fit the terminal box cover, making sure that the sealing surfaces are
clean.

;

Screw in the four screws (for tightening torque, see Chapter 3.1
Product drawing).

4.3.4 Cable routing

Water must be prevented from reaching the cable gland along the cable.

NOTE
Damage caused by moisture penetration.

Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable

glands, the cable should be routed in a U-shaped loop
wherever possible.

→ If this is not possible, a drip edge can be produced by

fitting a cable tie directly in front of the cable gland for example.

When routing the cable, make sure that the cable glands are located at
the bottom. The cables must always be routed downward.

4.4 Factory settings

Factory settings made for the device by ebm-papst.

Mode parameter set 1

Speed control

Mode parameter set 2

Speed control

Fan/device address

01

Max. PWM / %

100

Min. PWM / %

5

Save set value to
EEPROM

Yes

Set value requirement

Analog (linear)

Direction of action
parameter set 1

Positive (heating)

Direction of action
parameter set 2

Positive (heating)

Summary of Contents for R3G500- DA25-05

Page 1: ...199 1 8 017 399 83 88 E mail 5 v klapan by v klapan by EC Ebmpapst R3G500 DA25 05...

Page 2: ...otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electric...

Page 3: ...is possible e g in conjunction with open and closed loop control devices If impermissible radiation levels occur following installation appropriate shielding measures have to be taken by the user NOT...

Page 4: ...ce is to be used in networks with network quality characteristics as per EN 50160 Using the device only in stationary systems Performing all maintenance work Conveying air at an ambient air pressure b...

Page 5: ...g instructions 3 TECHNICAL DATA 3 1 Product drawing All dimensions in mm 1 Accessory part inlet ring 63072 2 4013 not included in scope of delivery 2 Max clearance for screw 20 mm 3 Cable diameter min...

Page 6: ...Operating instructions R3G500 DA25 05 Translation of the original operating instructions All dimensions in mm Inlet ring 63072 2 4013...

Page 7: ...other air conduction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regu...

Page 8: ...rrangement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected...

Page 9: ...mbol and a hole 4 2 2 Supply connection and fuses Assignment of supply cable cross sections and their required fuses line protection only no equipment protection Nominal voltage Fuse Automatic circuit...

Page 10: ...rdance with DIN 46228 1 for flexible cable 0 25 mm 1 5 mm NOTE Crimping and pressing forms of the wire end ferrules For flexible control and relay cables from a cable cross section of 1 0 mm a trapezo...

Page 11: ...nd along the cable NOTE Damage caused by moisture penetration Moisture can penetrate into the terminal box if water is constantly present at the cable glands To prevent the constant accumulation of wa...

Page 12: ...Analog input 0 10 V PWM Ri 100 k function Set value Characteristic curve parameterizable see input characteristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions ta...

Page 13: ...e high digital input not active pin open or applied voltage 1 5VDC active applied voltage 3 5 50VDC SELV D159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k...

Page 14: ...Operating instructions R3G500 DA25 05 Translation of the original operating instructions 4 7 Equivalent circuit diagrams...

Page 15: ...igh vibration levels and possibly resonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or find ano...

Page 16: ...Check line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning Faulty connection Isolate from supply correct connection see con...

Page 17: ...ation and perpendicular to this Fig 5 Example illustrating vibration measurement The arrangement of the sensors depends on the device concerned and the installation situation 6 3 Cleaning To ensure a...

Page 18: ...f the product must be performed or supervised by qualified personnel with the appropriate technical knowledge The product is to be disassembled into suitable components for disposal employing standard...

Reviews: