background image

Operating instructions

R3G900-AQ01-01

Translation of the original operating instructions

CAUTION
In the event of failure, there is electric voltage at the
rotor and impeller

The rotor and impeller are base insulated.
→ Do not touch the rotor and impeller once they are installed.

CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor automatically restarts, e.g. after a power failure.

Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains

supply voltage and secure the latter from being switched on
again.

→ Wait until the device stops.
→ After working on the device, remove any used tools or

other objects from the device.

1.5 Safety and protective functions

DANGER
Missing safety device and non-functioning safety device

If there is no safety device, you could be seriously injured, for
example if you reach into the running device or your hands are
sucked into it.
→ Operate the device only with a fixed and isolating safety

protection and a fixed guard grille.
The guard must withstand the kinetic energy of a fan blade
detaching at maximum speed.

→ The device is a built-in component. You, the owner/

operator, are responsible for providing adequate protection for
the device.

→ Shut down the device immediately if you detect a

missing or ineffective protective feature.

1.6 Electromagnetic radiation

NOTE
Electrical or electromagnetic interferences after
integrating the device in installations on the customer's
side.

→ Verify that the entire setup is EMC compliant.

1.7 Mechanical movement

DANGER
Rotating device

Body parts that come into contact with the rotor and impeller
can be injured.
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all

parts have come to a standstill.

DANGER
Flying parts

Missing safety devices may cause balancing weights or
broken fan blades to be ejected at high speeds, causing bodily
harm.
→ Take appropriate safety measures.

WARNING
Rotating device

Long hair, loose items of clothing and jewellery could become
entangled and pulled into the device. You could be injured.
→ Do not wear any loose clothing or jewellery while working

on rotating parts.

→ Protect long hair by wearing a cap.

1.8 Emission

WARNING
Depending on the installation and operating conditions,
a sound pressure level greater than 70 dB(A) may arise.

Danger of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety

equipment, e.g. hearing protection.

→ Also observe the requirements of local agencies.

1.9 Hot surface

CAUTION
High temperature at the electronics enclosure

Danger of burn injuries
→ Ensure that sufficient protection against accidental contact is

provided.

1.10 Storage

;

Store the device, partially or fully assembled, in a dry and
weatherproof manner in the original packing in a clean environment.

;

Protect the device from environmental impacts and dirt until the final
installation.

;

We recommend storing the device for a maximum up to one year to
guarantee proper operation and longest possible service life.

;

Even devices explicitly suited for outdoor use are to be stored as
described prior to being commissioned.

;

Maintain the storage temperature, see
chapter 3.6 Transport and storage conditions.

;

Please make sure that all screwed cable glands are fitted with
dummy plugs.

1.11 Disposal

When disposing of the device, please comply with all relevant
requirements and regulations applicable in your country.

Item no. 51307-5-9970 · ENG · Revision 82539 · Release 2014-05-08 · Page 2 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for R3G900-AQ01-01

Page 1: ...ecialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the device without the...

Page 2: ...til all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery...

Page 3: ...ing ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids content in flow medium Painting the device Connections e g screws coming loose during operation Opening the terminal box during operation St...

Page 4: ...d scope of delivery other inlet nozzles on request 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Cable diameter min 9 mm max 16 mm tightening torque 6 0 9 Nm 4 Depth of screw max 25 mm 5 Tightening torque 3 5 0 5 Nm Item no 51307 5 9970 ENG Revision 82539 Release 2014 05 08 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 ...

Page 5: ...bearing Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V Input for sensor 0 10 V or 4 20 mA External 24 V input programming External release input Alarm relay Integrated PID controller Motor current limit PFC passive RS485 MODBUS RTU Soft start Control input 2 bit Control interface with SELV potential safely disconnected from the mains Over temperature pro...

Page 6: ...distance to the power supply line when routing the control lines of the device Ensure a sufficiently large clearance Recommendation clearance 10 cm separate cable routing NOTE Water penetration into leads or wires Water enters at the cable end on the customers side and can damage the device Make sure that the cable end is connected in a dry environment Connect the device only to circuits that can ...

Page 7: ...ess than the nominal current FLA 4 3 Connection in terminal box 4 3 1 Preparing connection lines for the connection Strip the cable just enough so that the screwed cable gland is tight and the terminals are relieved of strain Tightening torque see chapter 3 1 Product drawing Fig 1 Recommended stripping lengths in mm inside the terminal box Legend CL control lines 4 3 2 Connecting cables with termi...

Page 8: ...ng Control mode parameter set 2 PWM controlling Fan device adress 01 Max PWM 100 Min PWM 8 Save set value to EEPROM Yes Set value control Analogue linear Control function parameter set 1 Positive heating Control function parameter set 2 Positive heating Item no 51307 5 9970 ENG Revision 82539 Release 2014 05 08 Page 8 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 ...

Page 9: ...en pin or applied voltage 5 50 VDC disabling bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 parameter set switch 1 2 according to EEPROM setting the valid used parameter set can be selected via bus or via digital input DIN2 Parameter set 1 open pin or applied voltage 5 50 VDC Parameter set 2 bridge to GND...

Page 10: ...e fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the device during operation Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work Switch off th...

Page 11: ...e Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again automatically without advance warning Faulty connection De energise correct connection see connection diagram Motor winding broken Replace device Insufficient cooling Improve cooling Let the d...

Page 12: ...inst accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage Visual inspec...