background image

Operating instructions

S3G450-LA14-71

Translation of the original operating instructions

CAUTION
In the event of failure, there is electric voltage at the
rotor and impeller

The rotor and impeller are base insulated.
→ Do not touch the rotor and impeller once they are installed.

CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor automatically restarts, e.g. after a power failure.

Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains

supply voltage and secure the latter from being switched on
again.

→ Wait until the device stops.
→ After working on the device, remove any used tools or

other objects from the device.

1.5 Safety and protective functions

DANGER
Missing safety device and non-functioning safety device

If there is no safety device, you could be seriously injured, for
example by reaching into the running device with your hands.
→ Operate the device only with a fixed and isolating safety

protection and a fixed guard grille. The guard must withstand
the kinetic energy of a fan blade detaching at maximum
speed.

→ The device is a built-in component. You, the owner/

operator, are responsible for providing adequate protection for
the device.

→ Shut down the device immediately if you detect a

missing or ineffective protective feature.

1.6 Electromagnetic radiation

Interference from electromagnetic radiation is possible, e.g. in conjunction
with open and closed-loop control devices.
If unacceptable emission intensities occur when the fan is installed,
appropriate shielding measures have to be taken by the user.

NOTE
Electrical or electromagnetic interferences after
integrating the device in installations on the customer's
side.

→ Verify that the entire setup is EMC compliant.

1.7 Mechanical movement

DANGER
Rotating device

Body parts that come into contact with the rotor and impeller
can be injured.
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all

parts have come to a standstill.

WARNING
Rotating device

Long hair, loose items of clothing and jewellery could become
entangled and pulled into the device. You could be injured.

→ Do not wear any loose clothing or jewellery while working

on rotating parts.

→ Protect long hair by wearing a cap.

1.8 Emission

WARNING
Depending on the installation and operating conditions,
a sound pressure level greater than 70 dB(A) may arise.

Danger of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety

equipment, e.g. hearing protection.

→ Also observe the requirements of local agencies.

1.9 Hot surface

CAUTION
High temperature at the electronics enclosure

Danger of burn injuries
→ Ensure that sufficient protection against accidental contact is

provided.

1.10 Storage

;

Store the device, partially or fully assembled, in a dry and
weatherproof manner in the original packing in a clean environment.

;

Protect the device from environmental impacts and dirt until the final
installation.

;

We recommend storing the device for a maximum up to one year to
guarantee proper operation and longest possible service life.

;

Even devices explicitly suited for outdoor use are to be stored as
described prior to being commissioned.

;

Maintain the storage temperature, see
chapter 3.6 Transport and storage conditions.

1.11 Disposal

When disposing of the device, please comply with all relevant
requirements and regulations applicable in your country.

Item no. 50855-5-9970 · Revision 70681 · Release 2010-07-29 · Page 2 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for S3G450-LA14-71

Page 1: ...onnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the device without the approva...

Page 2: ...tire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the devi...

Page 3: ... the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and protected accordingly Moving air that contains dust pollution e g suctioning off saw dust Operatin...

Page 4: ...e unit mm 1 Direction of air flow V 2 Connection line AWG 18 5x crimped core end sleeves 3 Connection line AWG 22 3x crimped core end sleeves Item no 50855 5 9970 Revision 70681 Release 2010 07 29 Page 4 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...peration mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 1 1 mA Alarm relay Motor current limit Soft start Control input 0 10 VDC PWM Over temperature protected electronics motor Line undervoltage detection Touch current acc IEC 60990 measuring network Fig 4 TN system 3 5 mA Motor protection Thermal overload protector TOP wired internally Cable exit Variable Protection clas...

Page 6: ...ge the device Make sure that the cable end is connected in a dry environment Connect the device only to circuits that can be switched off using an all pole disconnecting switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed fo...

Page 7: ...rap Fans installed in upright position Ill 2 Cable routing for fans installed in upright position The cables must always be routed downwards Item no 50855 5 9970 Revision 70681 Release 2010 07 29 Page 7 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 8: ...riginal operating instructions 4 4 Connection screen Item no 50855 5 9970 Revision 70681 Release 2010 07 29 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 9: ...he device during operation Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the supply voltage When disconnecting be sure to disconnect th...

Page 10: ...tector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device cool down To reset the error message switch off the mains supply voltage for a min of 25 s and switch it on again Ambient temperature too high Reduce the ambient temperature Reset by reducing control...

Page 11: ...6 months Open bore holes Weld seams for crack formation Visual inspection At least every 6 months Replace device Check the ball bearings to ensure they are quiet can move easily and are free of play Manual check by turning the rotor in shut off state At least every 6 months Replace device in case of noise difficulty of movement or clearance of the bearings Item no 50855 5 9970 Revision 70681 Relea...

Reviews: