Operating instructions

S6D560-AK01-03

Translation of the original operating instructions

4.5 Opening additional cable glands

A second cable gland opening can be made in the terminal box.

WARNING
In the event of a fault, the cable gland is energized

Electric shock
→ Do not use metal cable glands with plastic terminal boxes.

;

Screw the cable gland into the precut thread using a wrench. When
doing so, take note of the tightening torques; see Chapter 3.1 Product
drawing.

;

Remove the plastic tab that fell off inside the terminal box when it was
penetrated.

Fig. 4: Cable gland opening

NOTE
Tightness and strain relief are dependent on the cable
used.

→ This must be checked by the user.

4.6 Checking connections

;

Ensure isolation from supply (all phases).

;

Make sure a restart is impossible

;

Check the cables for proper fit.

;

Screw the terminal box cover back on again. Terminal box tightening
torque, see Chapter 3.1 Product drawing.

;

Make sure the terminal box is completely closed and sealed and that
all screws and cable glands have been properly tightened.

4.7 Switching on the device

The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical hookup. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.

WARNING
Hot motor housing

Risk of fire
→ Ensure that no combustible or flammable materials are

located close to the fan.

;

Before switching on, check the device for visible external damage
and make sure the protective devices are functional.

;

Check the fan's air flow paths for foreign matter and remove any
foreign matter found.

;

Apply the nominal supply voltage.

NOTE
Damage to the device from vibration

Bearing damage, shorter service life
→ Low-vibration operation of the fan must be ensured over the

entire speed control range. #Severe vibration can arise for
instance from inexpert handling, transportation damage and
resultant imbalance or be caused by component or structural
resonance. #Speed ranges with excessively high vibration
levels and possibly resonant frequencies must be
determined in the course of fan commissioning. #Either run
through the resonant range as quickly as possible with
speed control or find another remedy.# Operation with
excessively high vibration levels can lead to premature
failure.

4.8 Switching off the device

;

Disconnect the device from the power supply at the supply line's
main switch.

;

When disconnecting, be sure to disconnect the ground connection last.

5. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on your device. Send the device to ebm-
papst for repair or replacement.

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
The motor restarts automatically when operating voltage
is applied, e.g. after a power failure.

Risk of injury
→ Keep out of the device's danger zone.
→ When working on the device, switch off the line voltage

and ensure that it cannot be switched back on.

→ Wait until the device comes to a stop.
→ Install the externally wired thermal overload protector in

the control circuit so that following a malfunction the motor
does not switch on again automatically after cooling off.

If the device is out of use for some time, e.g. when in storage,
we recommend switching it on for at least two hours to allow
any condensation to evaporate and to move the bearings.

Malfunction/fault

Possible cause

Possible remedy

Impeller not
running smoothly

Imbalance in rotating
parts

Clean the device;
replace it if imbalance
persists after cleaning.
Make sure no
weight clips are
removed during
cleaning.

Motor not turning

Mechanical blockage

Switch off, isolate
from supply and
remove mechanical
blockage.

Item no. 10856-5-9970 · ENU · Change 91583 · Approved 2016-09-23 · Page 10 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for S6D560-AK01-03

Page 1: ...ined and otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the...

Page 2: ...the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and...

Page 3: ...prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration...

Page 4: ...s in mm 1 Direction of air flow V 2 Tightening torque 1 5 0 2 Nm 3 Cable diameter min 6 mm max 12 mm tightening torque 2 0 0 3 Nm Item no 10856 5 9970 ENU Change 91583 Approved 2016 09 23 Page 4 12 eb...

Page 5: ...v m h 4805 09 Pressure increase total psf Pa 85 10 Speed rpm n min 1 890 11 Specific ratio 1 00 12 Recycling disposal Information on recycling and disposal is provided in the operating instructions 13...

Page 6: ...ries Two people should work together to remove the device from its packaging NOTE Damage to the device from vibration Bearing damage shorter service life The fan must not be subjected to force or exce...

Page 7: ...residual current devices cannot provide personal safety while operating the device 4 2 3 Voltage control With speed control using transformers or electronic voltage regulators e g phase control excess...

Page 8: ...nect the device to circuits that can be switched off with an all pole disconnection switch When working on the device secure the system machine in which the device is installed so as to prevent it fro...

Page 9: ...tion Y Star connection L1 V1 blue L2 U1 black L3 W1 brown W2 yellow U2 green V2 white TOP 2x gray PE green yellow Item no 10856 5 9970 ENU Change 91583 Approved 2016 09 23 Page 9 12 ebm papst Mulfinge...

Page 10: ...e from inexpert handling transportation damage and resultant imbalance or be caused by component or structural resonance Speed ranges with excessively high vibration levels and possibly resonant frequ...

Page 11: ...ld on the basis of German standards Right from the development stage ecological design technical safety and health protection are fixed criteria The following section contains recommendations for ecol...

Page 12: ...mploying the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 10856 5 9970 ENU Change 91583 Approved 2016 09 23 Page 12 12 ebm papst Mulfinge...

Reviews: