background image

Operating instructions

S6E560-AK01-01

Translation of the original operating instructions

Fans installed upright

When routing the cable, make sure that the cable glands are located at
the bottom. The cables must always be routed downward.

Fig. 3: Cable routing for fans installed upright.

4.3.4 Motor protection

CAUTION
Voltage

The device is a built-in component and has no disconnecting
switch.
→ Connect the device to a suitable tripping unit.
→ Only connect the device to circuits that can be switched

off with an all-pole disconnection switch.

→ When working on the device, secure the system/

machine in which the device is installed so as to prevent it
from being switched back on.

NOTE
Lack of motor protection

Without motor protection, the motor can overheat and suffer
damage.
→ Connect the thermal overload protector installed in the

winding.

The motors are equipped with thermal overload protectors to protect the
devices.
Check to make sure that the thermal overload protector is correctly
connected before each operation.
Failure to connect the thermal overload protector correctly will
invalidate your warranty claim.

Item no. 10964-5-9970 · ENU · Change 98149 · Approved 2018-07-24 · Page 8 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for S6E560-AK01-01

Page 1: ...itably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 B...

Page 2: ...step on the guard grill or subject the guard grill to load Do not place any objects on the guard grill There must be sufficient space around the fan to be able to get past the fan 1 6 Mechanical move...

Page 3: ...ohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration tr...

Page 4: ...s in mm 1 Direction of air flow V 2 Tightening torque 0 8 0 15 Nm 3 Cable diameter min 6 mm max 12 mm tightening torque 2 0 3 Nm Item no 10964 5 9970 ENU Change 98149 Approved 2018 07 24 Page 4 12 ebm...

Page 5: ...tion of protective earth Motor capacitor according to EN 60252 1 in safety protection class S0 Conformity with standards EN 61800 5 1 Approval CCC EAC VDE With regard to cyclic speed loads note that t...

Page 6: ...ned on fastening 4 2 Electrical connection DANGER Voltage on the device Electric shock Always connect a protective earth first Check the protective earth DANGER Faulty insulation Risk of fatal injury...

Page 7: ...requency drives an all pole sine filter protects the motor against high voltage transients that can destroy the coil insulation system and against harmful bearing currents Heating up of the motor when...

Page 8: ...ice secure the system machine in which the device is installed so as to prevent it from being switched back on NOTE Lack of motor protection Without motor protection the motor can overheat and suffer...

Page 9: ...4 4 Connection diagram L U1 blue Z brown N U2 black PE green yellow TOP gray Item no 10964 5 9970 ENU Change 98149 Approved 2018 07 24 Page 9 12 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mul...

Page 10: ...tire speed control range Severe vibration can arise for instance from inexpert handling transportation damage and resultant imbalance or be caused by component or structural resonance Speed ranges wit...

Page 11: ...e Abnormal bearing noise acoustic At least every 6 months Replace device 5 3 Disposal For ebm papst environmental protection and resource preservation are top priority corporate goals ebm papst operat...

Page 12: ...The materials concerned are as follows Miscellaneous insulators used in the terminal box Power cables Cables for internal wiring Electrolytic capacitors Dispose of electronic components employing the...