6.1.2 Status codes

Manual reset by "Switch off line voltage - wait briefly - switch line
voltage back on" or, if provided,
via the "Fan enable/disable" input

Number of
pulses

Motor status -
LED red

Possible cause Possible

remedy

1

Phase failure or
line undervoltage

Missing phase
Poor power
supply quality

Check line
voltage

3

Output stage
overheating

Electronics
housing
contaminated

Provide better
cooling.
Manual reset
required

4

Communication
error between
master
controller and
slave controller

External
supply applied
via Vout for
setting
parameters.
Internal error

Switch off line
voltage
- wait -
switch back on

6

Motor
overheating

Ambient
temperature too
high
Impermissible
operating point

Reduce
ambient
temperature
Correct
operating point.
Manual reset
required

7

Hall sensor error Internal error

Switch off line
voltage
- wait -
switch back on

8

Motor blocked

Mechanical
blockage

Switch off
- check safe
isolation from
supply -
check
freedom of
movement of
rotor

9

Speed limit
exceeded

-

-

11

Rotor position
sensor
calibration error

Observe
ebm-papst
replacement
instructions

Rotor position
sensor
calibration
necessary.
Notify ebm-
papst

13

DC-link
undervoltage

Line voltage not
OK

Check the line
voltage applied.

6.2 Vibration testing

If the vibration sensor integrated in the fan’s motor is not to be used, the
following “manual” vibration test must be performed. This vibration test
must be performed for each fan separately and across the fan’s entire
speed range. Speed ranges with excessive vibration speeds are to be
avoided in continuous operation. The vibration test must be performed
every 6 months.
Checking of fan for mechanical vibration based on ISO 14694.
Recommendation: Every 6 months. Max. vibration severity is 3.5 mm/
s, measured at the motor fastening diameter on the motor support plate in
the direction of the motor axis of rotation and perpendicular to this.

Fig. 6: Example illustrating vibration measurement. The arrangement of
the sensors depends on the device concerned and the installation
situation.

6.3 Cleaning

To ensure a long service life, check the fans regularly for proper
operation and soiling. The frequency of checking is to be adapted
accordingly depending on the degree of soiling.

DANGER
Risk of injury from rotating fan.

→ Only clean when not in motion. Do not disconnect the fan

from the power supply, just switch it off via the control input.
This will prevent start-up of the fan.

;

Dirt deposits on the motor housing can cause overheating of the motor.

;

Soiling of the impeller can cause vibration that will shorten the service
life of the fan.

;

Severe vibration can destroy the fan.

;

In such cases, switch off the fan immediately and clean it.

;

The preferred method of cleaning is dry cleaning, e.g. using
compressed air.

;

Do not use aggressive cleaning agents!

NOTE
Damage to the device during cleaning

Malfunction possible
→ Do not clean the device using a high-pressure cleaner.# Do

not use acid, alkali or solvent-based cleaning agents.

→ Do not use any pointed or sharp-edged objects for

cleaning.

;

Completely remove any cleaning agents used.

;

If severe corrosion is visible on load-bearing or rotating parts, switch
off the device immediately and replace it.

;

Repair of load-bearing or rotating parts is not permitted!

;

Operate the fan for 2 hours at maximum speed so that any water that
has ingressed can evaporate.

;

If cleaning does not eliminate vibrations, the fan may need to be
rebalanced. To have it rebalanced, contact ebm-papst.

;

The fan is equipped with maintenance-free ball bearings. The lifetime
lubrication of the ball bearings is designed for a service life of 40,000
hours.

Item no. 1170000679 · ENU · Change 275056 · Approved 2023-01-27 · Page 15 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for VBH0500CTTRS

Page 1: ...re permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the dev...

Page 2: ...sures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical moveme...

Page 3: ...nly in stationary systems Performing all maintenance work Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Ch...

Page 4: ...14 mm tightening torque 6 0 9 Nm The tightening torque is designed for PVC cables If the cable materials are different the tightening torque may have to be adjusted 4 Tightening torque 3 0 3 Nm 5 Inl...

Page 5: ...air conduction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation...

Page 6: ...ith the network operator that this device is only connected to a connection point with an Ssc value greater than or equal to 250 times the rated output of the arrangement 4 CONNECTION AND STARTUP 4 1...

Page 7: ...east AWG 26 0 13 mm Protective earth contact resistance according to EN 61800 5 1 Compliance with the resistance specifications according to EN 61800 5 1 for the protective earth connection circuit mu...

Page 8: ...DIN 46228 1 for flexible cable 0 25 mm 6 mm NOTE The cable and cable cross section must be selected taking into account the max starting current of the drive and the type of cable routing see Chapter...

Page 9: ...Insert the strands until they meet with resistance Fig 5 Connection of cables at terminals There must not be any tensile stress between the terminal and the cable gland The cable must be provided with...

Page 10: ...ut characteristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Actual speed Characteristic curve par...

Page 11: ...SELV D159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k 10KHz SELV Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 a...

Page 12: ...inal operating instructions 4 6 Equivalent circuit diagrams Item no 1170000679 ENU Change 275056 Approved 2023 01 27 Page 12 16 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0...

Page 13: ...Switching off the device Switching off the device during operation Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching of...

Page 14: ...arts automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Inadequate cooling Improve cooling Allow the devi...

Page 15: ...ening diameter on the motor support plate in the direction of the motor axis of rotation and perpendicular to this Fig 6 Example illustrating vibration measurement The arrangement of the sensors depen...

Page 16: ...dations for ecological disposal of the product and its components 6 5 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific lega...

Reviews: