1.4 Voltage

;

Check the device's electrical equipment at regular intervals; see
Chapter 6.4 Safety inspection.

;

Replace loose connections and defective cables immediately.

DANGER
Electrically charged device

Risk of electric shock
→ When working on an electrically charged device, stand on a

rubber mat.

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
In the event of a fault, the rotor and the impeller will be
energized

The rotor and the impeller have basic insulation.
→ Do not touch the rotor and impeller once installed.

CAUTION
If control voltage or a stored speed set value is applied,
the motor will restart automatically, e.g. after a power
failure.

Risk of injury
→ Keep out of the device’s danger zone.
→ When working on the device, switch off the line voltage

and ensure that it cannot be switched back on.

→ Wait until the device comes to a stop.
→ After working on the device, remove any tools or other

objects from the device.

1.5 Safety and protective features

DANGER
Guard missing and guard not functioning

Without a guard, hands may become caught up in the device
during operation for example, resulting in serious injury. Loose
parts or items of clothing could be drawn in.
→ The device is a built-in component. As the owner, you are

responsible for ensuring that the device is adequately
safeguarded.# Operate the device only with a fixed
protective device and guard grill.

→ Stop the device immediately if a protective device is

found to be missing or ineffective.

1.6 Electromagnetic radiation

Interference from electromagnetic radiation is possible, e.g. in conjunction
with open- and closed-loop control devices.
If impermissible radiation levels occur following installation, appropriate
shielding measures have to be taken by the user.

NOTE
Electrical or electromagnetic interference after installing
the device in customer equipment.

→ Verify that the entire setup is EMC-compliant.

1.7 Mechanical movement

DANGER
Rotating device

Risk of injury to body parts coming into contact with the rotor or
the impeller.
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all

parts have come to a standstill.

DANGER
Ejected parts

Missing protective devices may cause balancing weights or
broken fan blades to be ejected and cause injuries.
→ Take appropriate safety measures.

WARNING
Rotating device

Long hair and dangling items of clothing, jewelry and the like
can become entangled and be pulled into the device. Injuries
can result.
→ Do not wear any loose-fitting or dangling clothing or jewelry

while working on rotating parts.

→ Protect long hair with a cap.

1.8 Emissions

WARNING
Depending on the installation and operating conditions,
the sound pressure level may exceed 70 dB(A).

Risk of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety

equipment such as hearing protection.

→ Also observe the requirements of local agencies.

1.9 Hot surface

CAUTION
High temperature on electronics housing

Risk of burns
→ Ensure sufficient protection against accidental contact.

1.10 Transport

WARNING
Transporting the fan

Injuries from tipping or slipping
→ The fan is always to be transported with care and in its

original packaging.

→ If set down too hard or at an angle for example, the

impact can lead to bearing damage or deformation of the
frame or impeller.

→ It must be ensured that the fans cannot tip over during

transportation and handling.

→ Secure the fan(s) with appropriate equipment such as a

lashing strip so that nothing can slip or tip, especially when
stacking multiple fans.

→ Also make allowance for possible wind forces.

Item no. 1170000679 · ENU · Change 275056 · Approved 2023-01-27 · Page 2 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for VBH0500CTTRS

Page 1: ...re permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the dev...

Page 2: ...sures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical moveme...

Page 3: ...nly in stationary systems Performing all maintenance work Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Ch...

Page 4: ...14 mm tightening torque 6 0 9 Nm The tightening torque is designed for PVC cables If the cable materials are different the tightening torque may have to be adjusted 4 Tightening torque 3 0 3 Nm 5 Inl...

Page 5: ...air conduction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation...

Page 6: ...ith the network operator that this device is only connected to a connection point with an Ssc value greater than or equal to 250 times the rated output of the arrangement 4 CONNECTION AND STARTUP 4 1...

Page 7: ...east AWG 26 0 13 mm Protective earth contact resistance according to EN 61800 5 1 Compliance with the resistance specifications according to EN 61800 5 1 for the protective earth connection circuit mu...

Page 8: ...DIN 46228 1 for flexible cable 0 25 mm 6 mm NOTE The cable and cable cross section must be selected taking into account the max starting current of the drive and the type of cable routing see Chapter...

Page 9: ...Insert the strands until they meet with resistance Fig 5 Connection of cables at terminals There must not be any tensile stress between the terminal and the cable gland The cable must be provided with...

Page 10: ...ut characteristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Actual speed Characteristic curve par...

Page 11: ...SELV D159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k 10KHz SELV Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 a...

Page 12: ...inal operating instructions 4 6 Equivalent circuit diagrams Item no 1170000679 ENU Change 275056 Approved 2023 01 27 Page 12 16 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0...

Page 13: ...Switching off the device Switching off the device during operation Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching of...

Page 14: ...arts automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Inadequate cooling Improve cooling Allow the devi...

Page 15: ...ening diameter on the motor support plate in the direction of the motor axis of rotation and perpendicular to this Fig 6 Example illustrating vibration measurement The arrangement of the sensors depen...

Page 16: ...dations for ecological disposal of the product and its components 6 5 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific lega...

Reviews: