3.2 Nominal data

Motor

M1G055-BD

Phase

1~

1~

Nominal voltage / VAC

230

230

Frequency / Hz

50/60

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

1500

1000

Power consumption / W

26

Current draw / A

0.2

Max. back pressure / Pa

36

Min. ambient
temperature / °C

-30

-30

Max. ambient
temperature / °C

50

50

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

1 kg

Size

230 mm

Motor size

55

Blade material

PA plastic

Fan housing material

PP plastic

Number of blades

5

Airflow direction

V

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP55

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H1+

Installation position

Any

Condensation
drainage holes

None

Mode

S1

Motor bearing

Ball bearing

Technical features

- Speed selection max./min.
- ESM+ expandable with plug-in
module
- Soft start
- Thermal overload protection for motor

Speed levels

2

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Lateral

Protection class

II

Conformity with
standards

EN 60335-1; EN 60335-2-24; EN 60335-
2-80; EN 60335-2-89; CE

Approval

EAC; UL 1004-3; CSA C22.2 No. 77;
VDE

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

3.4 Mounting data

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

For screw clearance, see Chapter 3.1 Product drawing

Strength class of
screws

8.8

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

3.5 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

-40 °C

3.6 Electromagnetic compatibility

EMC immunity to
interference

According to EN 61000-6-2 (industrial
environment)

EMC circuit feedback

According to EN 61000-3-2/3

EMC interference
emission

According to EN 61000-6-3 (household
environment)

Item no. 50086-5-9970 · ENU · Change 205631 · Approved 2019-07-26 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for W1G230-EB89-01

Page 1: ...trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules...

Page 2: ...up is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before w...

Page 3: ...Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the cu...

Page 4: ...s in mm 1 Direction of air flow V 2 Direction of rotation counterclockwise viewed toward rotor 3 Cable AWG20 3x crimped splices Item no 50086 5 9970 ENU Change 205631 Approved 2019 07 26 Page 4 11 ebm...

Page 5: ...questions consult ebm papst for support Use the device in accordance with its degree of protection Information on surface quality The surfaces of the products conform to the generally applicable indu...

Page 6: ...revent it from being switched back on NOTE Water ingress into wires or cables Water ingress at the customer end of the cable can damage the device Make sure the end of the cable is connected in a dry...

Page 7: ...st always be routed downward NOTE Cable routing is to be performed accordingly if use is made of the ESM plug in module to connect the fan Item no 50086 5 9970 ENU Change 205631 Approved 2019 07 26 Pa...

Page 8: ...ting instructions 4 4 Connection diagram Drawing preliminary Item no 50086 5 9970 ENU Change 205631 Approved 2019 07 26 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49...

Page 9: ...n the event of the faults described in the table Fault Safety feature description function Rotor position detection error An automatic restart follows Blocked rotor After the blockage is removed the m...

Page 10: ...an evaporate If cleaning does not eliminate vibrations the fan may need to be rebalanced To have it rebalanced contact ebm papst The fan is equipped with maintenance free ball bearings The lifetime lu...

Page 11: ...num Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Onl...

Reviews: