Operating instructions

W3G350-SN01-30

Translation of the original operating instructions

3.5 Mounting data

Further mounting data can be taken from the product drawing or Chapter
4.1 Mechanical connection as required.

Strength class of
screws

8.8

For screw clearance, see Chapter 3.1 Product drawing

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

3.6 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 70 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

3.7 Accessories

3.7.1 AxiCool heating tape

A heating tape that can be installed in the fan housing is available for the
AxiCool fans. To prevent ice formation, ebm-papst recommends the use
of a heating tape for all applications below 0 °C. The heating tape
designed for the AxiCool fan housing is available from ebm-papst under
the following item numbers.

Fan size

Item no.

300 mm

00300-2-7680

350 mm

00350-2-7680

450 mm

00450-2-7680

During assembly, comply with the installation instructions included with
each ebm-papst heating tape.
ebm-papst assumes no liability when heating tapes from other
manufacturers are used. Note the maximum permitted temperature of
+60 ± 5 °C for the heating tape to prevent damage to the wall ring.

4. CONNECTION AND STARTUP

4.1 Mechanical connection

CAUTION
Cutting and crushing hazard when removing device
from packaging

Blades can bend
→ Carefully remove the device from its packaging, by the fan

housing. Strictly avoid shocks.

→ Wear safety shoes and cut-resistant safety gloves.

CAUTION
The blades of the impeller could be damaged.

→ Carefully set down the fan on a soft surface. Make sure the

blades are not subjected to load.

→ Following installation, make sure the impeller moves

easily and that the blades of the impeller are not deformed or
bent and do not catch at any point.

NOTE
Damage to the device from vibration

Bearing damage, shorter service life
→ The fan must not be subjected to force or excessive vibration

from sections of the installation.

→ If the fan is connected to air ducts, the connection should

be isolated from vibration, e.g. using compensators or similar
elements.

→ Ensure stress-free attachment of the fan to the

substructure.

;

Check the device for transport damage. Damaged devices are not to
be installed.

;

Install the undamaged device in accordance with your application.

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

The fan must not be strained on fastening.

4.2 Electrical connection

DANGER
Voltage on the device

Electric shock
→ Always connect a protective earth first.
→ Check the protective earth.

DANGER
Faulty insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

regulations for voltage, current, insulation material, capacity,
etc.

→ Route cables so that they cannot be touched by any

rotating parts.

Item no. 52111-5-9970 · ENU · Change 274903 · Approved 2023-01-16 · Page 6 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for W3G350-SN01-30

Page 1: ...uitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3...

Page 2: ...ding measures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanica...

Page 3: ...prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration...

Page 4: ...ng All dimensions in mm 1 Direction of air flow V 2 Cable PVC 4G 0 5 mm 4x crimped splices 3 Mounting dimensions Item no 52111 5 9970 ENU Change 274903 Approved 2023 01 16 Page 4 11 ebm papst Mulfinge...

Page 5: ...ot fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article 2 2a motors completely integrated into a product 3 4 Technical description Weight 5 2 kg Size 350 mm Motor...

Page 6: ...d cut resistant safety gloves CAUTION The blades of the impeller could be damaged Carefully set down the fan on a soft surface Make sure the blades are not subjected to load Following installation mak...

Page 7: ...N 60335 for the protective earth connection circuit must be verified in the end application Depending on the installation situation it may be necessary to connect an additional protective earth conduc...

Page 8: ...230 VAC 50 60 Hz see nameplate for voltage range CON 11 N blue Neutral conductor CON 12 PE green yellow Protective earth CON 70 SL brown Speed selection switch open speed 1 switch closed speed 2 Item...

Page 9: ...d connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the event of the faults described in the table Fault Safety featur...

Page 10: ...rings is designed for a service life of 40 000 hours If bearing replacement is necessary after that period contact ebm papst Adapt the maintenance intervals to the actual level of dust exposure 6 2 Sa...

Page 11: ...num Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Onl...