background image

Operating instructions

W3G500-DN33-02

Translation of the original operating instructions

Fans installed upright

Fig. 2: Cable routing for fans installed upright.
The cables must always be routed downward.

Item no. 51876-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 8 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for W3G500-DN33-02

Page 1: ...used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product Note the following when working on...

Page 2: ... the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and cause injuries Take appropriate safety measures WARNING Rotating device Long hair and dangling items of clothing jewelry and the ...

Page 3: ...ng instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Operation in medical equipment with a life sustaining or life support function Operation with external vibrations Conveying solids in the flow medium Painting the device Connections e g screw...

Page 4: ...l dimensions in mm 1 Direction of air flow A 2 Cable PVC AWG22 6x crimped ferrules 3 Cable PVC AWG18 4x crimped ferrules Item no 51876 5 9970 ENU Change 89187 Approved 2016 04 15 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...combination in a standardized measurement setup 3 4 Technical description Weight 17 3 kg Fan size 500 mm Rotor surface Painted black Electronics housing material Die cast aluminum painted black Blade material Press fitted sheet steel blank sprayed with PP plastic Fan housing material Sheet steel galvanized and coated with black plastic RAL 9005 Guard grille material Steel coated with black plastic...

Page 6: ...packaging by the fan housing Strictly avoid shocks Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when unpacking device Risk of physical injury such as back injuries Two people should work together to remove the device from its packaging Check the device for transport damage Damaged devices are not to be installed Install the undamaged device in accordance with your applicati...

Page 7: ... 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 3 PE AC 380 480 VAC 32 A 30 A C32A 6 0 10 AWG American Wire Gauge 4 2 3 Reactive currents Because of the EMC filter integrated for compliance with EMC limits interference emission and immunity to interference reactive currents can be measured in the supply line even when the motor is at a standstill and the lin...

Page 8: ...upright Fig 2 Cable routing for fans installed upright The cables must always be routed downward Item no 51876 5 9970 ENU Change 89187 Approved 2016 04 15 Page 8 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 9: ... 250 VAC min 10 mA AC1 1 7 NC white 2 Floating status contact break for failure 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 kOhm SELV 2 11 10 V red Voltage output 10 VDC 3 max 10 mA power supply for external devices e g potentiometers SELV 2 12 GND blue Reference ground for control interface SELV Item no 51876 5 9970 ENU Change 89187 Approved 2016 04 15 Page 9 12 ebm papst Mul...

Page 10: ...tion detection error An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically Line undervoltage line voltage outside of permitted nominal voltage range If the line voltage returns to permitted values the motor restarts automatically Phase failure A phase of the supply voltage fails for at least 5 s When all phases are correctly supplied again the mo...

Page 11: ...gents Do not use any pointed or sharp edged objects for cleaning 6 2 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing voltage is applied Test the device with DC voltage when you perform the legally required high voltage test The voltage to be used corresponds to the peak value of the AC voltage required by the stan...

Page 12: ...etallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets a...

Reviews: