Operating instructions

W3G800-GV10-11

Translation of the original operating instructions

3. TECHNICAL DATA

3.1 Product drawing

All measures have the unit mm.

1

Direction of air flow "V"

2

Cable diameter: min. 4 mm, max. 10 mm, tightening torque: 4±0.6 Nm

3

Tightening torque 3.5±0.5 Nm

Item no. 50925-5-9970 · ENG · Revision 82270 · Release 2014-08-26 · Page 4 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for W3G800-GV10-11

Page 1: ...l the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the device without the approval of ebm papst 1 4 Electr...

Page 2: ...ANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect ...

Page 3: ...vice in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids content in flow medium Painting the device Connections e g screws coming loose during operation Opening the terminal box d...

Page 4: ...e the unit mm 1 Direction of air flow V 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm Item no 50925 5 9970 ENG Revision 82270 Release 2014 08 26 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...ensor 0 10 V or 4 20 mA External 24 V input programming Alarm relay Integrated PID controller Motor current limit PFC passive RS485 MODBUS RTU Soft start Control input 0 10 VDC PWM Control interface with SELV potential safely disconnected from the mains Over temperature protected electronics motor Line undervoltage phase failure detection Touch current acc IEC 60990 measuring network Fig 4 TN syst...

Page 6: ...gether Check the device for transport damage Damaged devices must no longer be installed Install the undamaged device according to your application 4 2 Connecting the electrical system DANGER Electric voltage on the device Electric shock Always install a protective earth first Check the protective earth DANGER Incorrect insulation Risk of fatal injury from electric shock Use only cables that meet ...

Page 7: ... measured even when the motor is at a standstill and the mains voltage is switched on The values lie in a range of typical 250 mA The effective power in this operating state readiness for operation is simultaneously at typical 5 W 4 2 4 Residual current operated device Only universal type B or B RCD protective devices are permitted Like frequency inverters RCD protective devices cannot provide per...

Page 8: ...rranged at the bottom The cables must always be routed downwards Fig 4 Cable routing for fans installed upright 4 4 Factory settings Factory settings with which the device is pre set by ebm papst Control mode parameter set 1 PWM controlling Control mode parameter set 2 PWM controlling Fan device adress 1 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes Set value control Analogue linear Control f...

Page 9: ...en pin or applied voltage 5 50 VDC disabling bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 parameter set switch 1 2 according to EEPROM setting the valid used parameter set can be selected via bus or via digital input DIN2 Parameter set 1 open pin or applied voltage 5 50 VDC Parameter set 2 bridge to GND...

Page 10: ...e fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the device during operation Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work Switch off th...

Page 11: ...e Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again automatically without advance warning Faulty connection De energise correct connection see connection diagram Motor winding broken Replace device Insufficient cooling Improve cooling Let the d...

Page 12: ...ive casing against accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage...