Operating instructions - SBU IO-Link
Page 33 of 50
Jumper
J1
+3.3 V reference for
Set
Not set
Power supply for
Bluetooth module
Bluetooth module active
Bluetooth module inactive
J7
GND reference for
Set
Not set
Power supply
solenoid valves GND
GND related to operating
voltage GND
0V potential for the SV
connections must be
applied separately to the
respective terminal (see
wiring diagram)
J8
Control SV1
Set
Not set
Control via
IO-Link / external
Control via IO-Link
Control by external signal
J9
Control SV2
Set
Not set
Control via
IO-Link / external
Control via IO-Link
Control by external signal
Danger due to incorrect operation.
Malfunctions of, or damage to components.
The SBU IO-Link may only be connected by an electrician.
For external control signals for the solenoid valves, the jumpers J7, J8 and J9
must
be removed
and the wiring diagram must be observed.
CAUTION