CPX230NWB ALARM CONTROL PANEL – INSTALLER MANUAL
73 / 144
EN
6.3.1.2.
Response type
Instant
– disruption of the zone causes immediate alarm, if the system is armed.
Delay
– that type of zone is usually used for detectors operation at the facility entries.
The zone switches into alarm state after the expiration of programmed time for entry.
If the system is armed, the zone activation initiates counting the time for entry to a
particular partition. The system should be disarmed before the expiration of
programmed time in order not to trigger the alarm.
24h burglary
– that zone causes immediate alarm irrespectively of whether the
system is armed or not.
Arming/disarming by violation
– the zone can be used for arming or disarming the
system. In case the zone is activated with the system disarmed, the partition assigned
to the zone is armed. In case the zone is activated with the system armed, the
partition assigned to the zone is disarmed.
Note:
For wired zones, it is recommended to configure them as NC or NO for this
response type.
24h tamper
– the zone can be used for connecting tamper/sabotage circuits. In case
of trigger when partition is disarmed, it generates “violation of the zone” event without
the alarm. In case of trigger when partition is armed, it generates “violation of the
zone” event and raises the alarm.
Interior delay
– the zone can be used when keypad is not in the first partition which
could be triggered during access to the keypad. In case of the interior delay partition is
triggered, system checks if time for enter is counting. If yes, the zone is treated as
delay zone. If not, the lien is treated as instant zone.
24h burglary silent
– sends a report to the central station but provides no keypad
display or sounding.
24h fire
– works like 24h burglary.
Perimeter
– This zone will be armed immediately after arm command. Detectors
protecting the entrance to the building (doors and windows) are defined like this.
Violation of this zone will raise the alarm, even during the exit time countdown.
Perimeter exit
– If the system is armed only by using a code, without selecting the
arming mode, violating this zones during exit time countdown will arm the system in
the fully armed mode. If this is not violated during exit time countdown, partition will
be armed in the stay mode. If the system is armed and a mode is selected, then
triggering this zone during the exit time countdown will be ignored, and the system will
be armed in the selected mode. If the system is armed, this zone behaves like the
delayed zone.
24h gas −
works like 24h burglary.
24h water leakage −
works like 24h burglary.
Night (bypassed) −
this zone is used for detectors located in places where humans
move around during the night. Violation of this zone will not trigger an alarm when the
system is armed in sleep mode. When the system is armed in full mode, the zone will
behave like an instant.