EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

 

 Model 

GTM116-B

  

Installation Guide

 

 

Gold Series 

Thermal Dispersion Airflow Measurement Technology

 

 

 

 

Advantage III 

Gold

 Series by Ebtron 

 

Installation Guide 

GTM116-B

 

“Plug & Play” Transmitter with Bleed Airflow Sensors, 

Combination Ethernet Network Output and Dual Analog Output 

 
 

Document Name: IG_GTM116-B_R1B 

 

 

 

 

  

a measurable difference! 

EBTRON 

BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or 
test products for compliance with ASHRAE standards. Compliance of listed products to 
the requirements of ASHRAE Standard 135 is the responsibility of BACnet International 
(BI). BTL is a registered trademark of BI. 

Models

 

GTC116

 

and

 

GTM116

 

Part

 

Number

 

930

0016B

 

LISTED 

 

 

European

 

Union

  

Shipments

 

Summary of Contents for Advantage III Gold Series

Page 1: ...rflow Sensors Combination Ethernet Network Output and Dual Analog Output Document Name IG_GTM116 B_R1B a measurable difference EBTRON BACnet is a registered trademark of ASHRAE ASHRAE does not endorse...

Page 2: ...TER START UP INITIALIZATION AND SETUP MENUS 11 5 1 Changing the System of Units IP or SI Units 11 5 2 GTM116 Transmitter Calibration 11 5 3 GTM116 LCD Display Notifications 11 5 4 Factory Default Menu...

Page 3: ...re 4 Type B Transmitter Connector Panel Detail 7 Figure 5 Connector Detail 7 Figure 6 GTM116 Combination Analog Ethernet Transmitter Interior Detail 8 List of Tables Table 1 GTM116 Power Transformer S...

Page 4: ...in 50 8 mm to each side and 3 5 in 88 9 mm below the transmitter to allow for cover removal sensor connections and heat dissipation Locate the transmitter in a location that can be reached by all conn...

Page 5: ...ed LCD contrast Transmitter status LED Green 1 second flash normal 2 second flash for fault High accuracy A D converter Gold plated interconnects to optional output cards Positive locking cable recept...

Page 6: ...VA Req 1 12 5 14 2 13 6 15 3 13 7 15 4 14 8 16 3 2 Connecting Power to the Transmitter Connect 24 VAC power to the large two position power input terminal labeled POWER on the upper right hand side o...

Page 7: ...de a drip loop at the transmitter if there will be the potential for water runoff or condensation along the bleed sensor cable s Bleed sensor cable plugs are keyed as shown below Line up plug with rec...

Page 8: ...o wire the analog outputs slide the cover plate up and off of the enclosure Ensure that the power switch is in the OFF position Connect signal wires for airflow rate or equivalent differential pressur...

Page 9: ...digit address segment that is under change Change the blinking segment by pressing the UP or DOWN buttons to arrive at the desired segment setting Depress the ENTER key to set this segment and to mov...

Page 10: ...nsert 1 Flow 30019 30020 Insert 4 Flow 4 30021 30028 float F Temperature Traverse 20 to 160 30021 30022 Insert 1 Temp 30027 30028 Insert 16 Temp 4 30029 30030 float Sq Ft Area 0 to 100 4 300202 word F...

Page 11: ...s are shown in IP System Of Units When SI System of Units is selected the units of measure abbreviations used in the menus is shown in Table 5 IP System of Units Description SI System of Units Descrip...

Page 12: ...set factor 0 000 0 000 AO2 SGNL Output 2 signal voltage or mA temperature or alarm mA see alarms mA see alarms AO2 MS Output 2 signal minimum scale 20 F 30 C AO2 FS Output 2 signal full scale 160 F 70...

Page 13: ...desired the output can be set to provide standard airflow measurement units displayed as SCFM and SFPM which provides measurements that are corrected to standard conditions 5 5 4 Output Scaling EBTRON...

Page 14: ...and AO2 alarm output indications User can select either or both of the two Average Alarms or the Trouble Alarm 5 6 5 Low Alarm LO ALRM ON The Low Alarm is activated when the average airflow falls belo...

Page 15: ...ntrol system To set a fixed output signal for airflow and temperature navigate to the OUTPUT TEST submenu in the TOOLS menu OUT1 and OUT2 tests are independently accessed and the output will maintain...

Page 16: ...odbus networks or via EB Link Reader Airflow and temperature of individual sensors can be read across BACnet or Modbus networks or downloaded directly to an EB Link Reader if the infra red EB Link opt...

Page 17: ...cters for blank or unwanted text EXT CABLE 0 SET EXT CABLE EXT CABLE 0 LCD TRBL ON Set measurement mode to AIRFLOW MEAS PRESS LCD DSPL BOTH SETUP Instruction text USE AND ENT then NAME _ GENERAL SET O...

Page 18: ...ate this setting is fixed and cannot be modified AO1 ASGN iWG AO1 UM FIXED The text AO1 UM FIXED flashes to indicate that this setting is fixed and cannot be modified ANALOG OUT AO1 ASGN FLOW SET AO1...

Page 19: ...ve to right and ESC to move to left Set network device instance number Set network protocol type Enter gateway IP address use up down arrow buttons to select value and press ENT to move to right and E...

Page 20: ...low alarm setpoint Units based on ALARM UM DELAY 2 MIN SET DELAY DELAY 2 MIN Enter alarm delay RESET AUTO SET RESET RESET AUTO Set alarm RESET AUTO will clear once the alarm is not active MANUAL requi...

Page 21: ...Adjust Wizard will now be engaged as outlined in the following steps The GAIN and OFF values will be updated and PRESS ADJ ON will be set if the wizard is successfully completed OF PRESS 2 OUT2 TEST...

Page 22: ...RESET ADJ NO RESET ALL NO Sets security level to MED In this mode a user defined code is specified In the event of loss of code contact EBTRON for a unique code for this transmitter to unlock and rese...

Page 23: ...te 2 L2 L1 POWER 24VAC IN OUT 1 AIRFLOW PRESSURE OUTPUT SIGNAL 1 2 COM ANALOG OUTPUT OUT 2 TEMP OR ALARM OUTPUT SIGNAL ANALOG BAS INTERFACE OUT 2 can be set as an analog Temperature Alarm or Trouble o...

Page 24: ...1663 Hwy 701 S Loris SC 29569 Toll Free 800 2EBTRON 232 8766 Fax 843 756 1838 Internet EBTRON com IG_GTM116 B_R1A GOLD SERIES GTM116 B TRANSMITTER a measurable difference EBTRON a measurable differen...