AIR-IQ PROBE  

INTERNAL MOUNT INSTALLATION

 

OVERVIEW 

 

This document provides the instructions necessary 
to install AIR-IQ Internal Mount Probes as shown in 
Figure 1. Internally mounted probes are installed 
inside of the damper sleeve. Installation consists of 
installing and securing the probes. For detailed 
probe information, refer to the Duct/Plenum Probe 
technical manual TM_GP1 under separate cover. 
For detailed information on transmitter set up and 
operation of the complete airflow measurement 
station, refer to the associated transmitter technical 
manual under separate cover.  
 
 

AIR-IQ INTERNAL MOUNTING  

Figure 2 provides AIR-IQ Internal Mount probe 
installation details. Probes are installed from inside 
of the damper sleeve using the included brackets. 
AIR-IQ Internal mount probes are manufactured 
shorter to permit 0.75 in (19 mm) adjustment and 
allow for installation clearance. Convenient check 
boxes are provided at each step.

 

 

1. 



Loosen the Non-Cable End Adjustment Screws on both sides of the probe as shown in the detail of Figure 2 

for AIR-IQ Probes to permit pivoting the probe and bracket. 
2. 

 

Carefully place the Non-Cable End bracket at the non cable end previously prepared location on the inside of 

the damper sleeve wall so that when the probe is installed, airflow will be in the direction of the arrows printed on 
the bracket and/or probe. For ease of installation, the probe can pivot within the bracket after loosening the Non-
Cable End Adjustment screws (completed in step 1). 

 

NOTE: 

If the airflow direction labels are not visible on the bracket and/or probe, orient the probe 

so that the sensor SET SCREWS (two per sensor insert) face the DOWNSTREAM airflow 

direction. (There are no setscrews on the upstream side of the sensor inserts). 

 

3. 



Fasten the Non-Cable End mounting bracket to the damper sleeve at two places with appropriate field 

supplied fasteners, again making sure that printed airflow arrows on the bracket and/or probe are in the actual 
direction of duct air flow.

 

4. 

  Carefully route the probe cable through the cable exit hole, and pivot the cable end probe bracket to the 

previously prepared location on the damper sleeve wall.

 

5.  



Fasten the cable end mounting bracket to the damper sleeve at two places with appropriate field supplied 

fasteners, again making sure that printed airflow arrows on the bracket and/or probe are in the actual direction of 
duct air flow. 
6. 

  Slightly loosen the cable end probe Adjustment screws on both sides of the probe to permit probe movement 

within the bracket.

 

Figure 1. AIR-IQ Internal Mount Probe