3.2 Parameters of MA01-AXCX4020
Category
Name
Parameter
Power
supply
Operating Voltage
DC 8
~
28V
Working current
50mA @ 12V
Power indicator
Green LED indication
Serial port
Communication
Interface
RS485
Baud rate
1200
~
115200 bps (default 9600 bps)
Check Digit
No parity, odd parity, even parity (no parity by
default)
Data bit
5,6,7,8
(
default 8
)
Stop bit
1,1.5,2 (defacult 1)
Protocol
Modbus RTU protocol
Device address
1
~
247 (default address: 1)
DI
Number of DI
4 way
Interface Type
Dry node
Trigger method
Rising edge, falling edge, level (default
level)
Filter parameter
1
~
16 (default 6)
Acquisition
frequency
1 kHz
Input instructions
Green LED indication
DO
Number of DO
4 way
DO output type
Type C relay (normally open + normally
closed)
DO output mode
Level mode, pulse mode
Relay contact
capacity
30V/10A, 250V/10A
Output indication
Red LED indication
Others
Product Size
80 mm * 50mm * 30mm (length * width *
height)
product weight
80g
±
5g
Working
temperature and
humidity
-40
~
+85
℃
, 5%
~
95%RH
(non-condensing)
Storage temperature
and humidity
-60
~
+125
℃
, 5%
~
95%RH
(non-condensing)
Installation method
Installation of guide rail and locating hole