Chengdu Ebyte Electronic Technology Co., Ltd.
【
4DI+2DO
】
MA01-AXCX4020 User Manual
Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
12
Chart 3-5-2 Position hole installation
4 Detailed function
4.1 Switch input DI
4.1.1 Switch input DI collection
Switch input DI to measure level signal or edge pulse signal (rising edge, falling edge). Support dry
node collection, support DI counting function, the maximum count is 65535 (the count is
automatically cleared when 65535 is exceeded).
The switch input DI supports three trigger modes: rising edge, falling edge, and level (the default
level trigger mode).
The clearing method supports automatic clearing and manual clearing (default automatic clearing).
4.1.2 Switch input DI filter parameters
When the switch inputs the DI to collect the signal, it needs to keep multiple sampling periods before
confirming. The filter parameter can be set from 1 to 16 (default 6 sampling periods). The DI filter
parameters can be set through the configuration software.