• Water Pressure Sensor
Subject
De
fi
ni
�
on
Part’s Function
1- The component that measures the water pressure in the central heating circuit.
Impact in Case of Malfunction
1- The device gives a low or high water pressure error.
2- The user sees a different water pressure value than the actual value.
3- The user may not see an increase in the pressur e even after filling the system with water.
Main Associated Error
Codes
F37, F40, F47
Error Diagnostics and Test
Method
Visual Inspection and Testing:
1- Ensure that the cable connections are properly done and undamaged.
2- Check whether the inlet hole of the water pressure sensor is blocked
3- Measure the voltage.
Maintenance Requirement
There is no special maintenance requirement.
Test Descrip
�
on
Test Method
Water Pressure Sensor
When the device is connected to power, remove the electrical connector on water the
pressure sensor and measure the DC voltage between the "IN"-"GND" ends as shown below.
Ensure the value is in the 4.9-5.1 VDC range.
Table 2
3
74