Test Descrip
�
on
Test Method
3-way Motorized Valve
Voltage and Position Check
(Domestic Water Heating)
Turn on the domes
�
c water while the device is plugged in. Measure the voltage on the
motorized valve connector at the part between A-B in the domes
�
c water hea
�
ng mode.
Ensure the value is in the 215-240 VAC range. The motorized valve pin should be at the
back part.
Subject
De
fi
ni
�
on
Part’s Function
When the water pressure in the central heating system reaches 3 bar, it opens the discharge
end and discharges the excess water.
Impact in Case of Malfunction
1- May cause low pressure error due to excessive water discharge.
2- May cause high pressure error due to no water discharge.
3- There is a risk of leakage in installation if the user continues to fill water after high
pressure error.
Main Associated Error
Codes
F37, F40
Error Diagnostics and Test
Method
1
-
Check for water leakage from the safety valve tip when the water pressure in the central
heating circuit is in the 0.8-2.5 bar range.
2
-
Measure the opening pressure.
Maintenance Requirement
There is no special maintenance requirement.
Test Descrip
�
on
Test Method
Safety Valve On-Off Pressure
Test
Fill the central heating system with water by opening the filling tap. The safety valve should
start discharging due to high water pressure in the 2.7-3.3 bar range and continue the
discharge until the water pressure drops to 2.5-2.7 bar range.
• 3-bar Safety Valve
Table 2
5
Table 2
6
76