EXCEL 50 INSTALLATION INSTRUCTIONS

25

EN1B-0101

L

ON

W

ORKS

 Network Interface

Excel 50 Controllers may be equipped with an application

module (see Table 15) containing an FTT-10A Free Topology

Twisted Pair Transceiver which allows communication with

other device on a L

ON

W

ORKS

 network. FTT-10A transceivers

communicate at 78 Kbaud and provide transformer isolation

so that the bus wiring does not have a polarity; that is, it is

not important which of the two bus terminals are connected

to each wire of the twisted pair.

LEDs

C-BUS TxD, YEL

POWER, GRN

C-BUS RxD, YEL

LON SERVICE, RED

RESERVED

00

00

01

24

C-BUS

SH

IE

L

D

C + C -

4 5 6

LON
BUS

NO

T

 US

E

D

A1 A2

1 2 3

LON SERVICE BUTTON

C-BUS
TERMINATION
SWITCH

Fig. 45. LonWorks network connection.

FTT devices can be wired in daisy chain, star, loop or any

combination thereof as long as the maximum wire length re-

quirements given below are met. The recommended con-

figuration is a daisy chain with two bus terminations. This

layout allows for maximum bus length, and its simple struc-

ture presents the least number of possible problems, par-

ticularly when adding on to an existing bus.

NOTE:

A doubly-terminated bus may have stubs of up to

10 ft (3 m) from the bus to each node.

Table 20. Doubly-terminated bus specifications.

Cable Type

Max. bus length

Belden 85102

2,700 m (8,900 ft)

Belden 8471

2,700 m (8,900 ft)

Level IV, 22 AWG

1,400 m (4,600 ft)

JY (St) Y 2x2x0.8

900 m (3,000 ft)

TIA568A Categ. 5 24AWG, twisted pair

900 m (3,000 ft)

NOTES:

The cable types listed above are as recommended by

Echelon in their FTT-10A User Guide. The cable re-

commended by Honeywell is the level IV, 22 AWG, solid

core, nonshielded cable. Belden part numbers are

9H2201504 (plenum) and 9D220150 (non-plenum).
The FTT specification includes two components that must be

met for proper system operation. The distance from each

transceiver to all other transceivers and to the termination

must not exceed the 

maximum node-to-node distance

. If

multiple paths exists, the 

maximum total wire length

 is the

total amount of wire used.

Table 21. Free topology (singly-terminated)

specifications.

Cable type

Maximum node-

to-node distance

Maximum total

wire length

Belden 85102

1,650 ft (500 m)

1,650 ft (500 m)

Belden 8471

1,300 ft (400 m)

1,650 ft (500 m)

Level IV, 22AWG

1,300 ft (400 m)

1,650 ft (500 m)

JY (St) Y 2x2x0.8

1,050 ft (320 m)

1,650 ft (500 m)

TIA568A Category 5
24AWG, twisted pair

825 ft (250 m)

1,500 ft (450 m)

IMPORTANT

Do not use different wire types or gauges on the

same L

ON

W

ORKS

 network segment. The step change

in line impedance characteristics would cause

unpredictable reflections on the network.

NOTE:

In the event that the limit on the total wire length is

exceeded, then FTT physical layer repeaters

(FTT 10A) can be added to interconnect segments

and increase the overall length by an amount equal

to the original specification for that cable type and

bus type for each repeater used. For example,

adding repeaters for a doubly-terminated bus using

JY (St) Y 2x2x0.8 cable increases the maximum

length 3,000 ft (900 m) for each repeater.

L

ON

W

ORKS

 Bus Termination

One or two Termination Modules, part no. 209541B, are re-

quired for a L

ON

W

ORKS

 Bus with FTT devices on it, de-

pending upon the configuration. The maximum lengths des-

cribed in the previous section must be adhered to for either a

daisy chain or free topology L

ON

W

ORKS

 network layout. See

Fig. 46 and Fig. 47 for connection details for the 2095401B

Termination Module.

Fig. 46. Termination Module connections for doubly-

terminated FTT network.

Fig. 47. Termination Module connections for a singly-

terminated FTT network.

(optional)

Summary of Contents for Excel 50

Page 1: ...EN1B 0101GE51 R1000 Excel 50 CONTROLLER INSTALLATION INSTRUCTIONS...

Page 2: ...Builder NodeBuilder LonManager LonTalk LonUsers LonPoint Neuron 3120 3150 the Echelon logo the LONMARK logo and the LonUsers logo are trademarks of Echelon Corporation registered in the United States...

Page 3: ...6 Technical Specification 16 Connection Examples 16 Analog Inputs 17 Technical Description 17 Technical Specification 17 Relay Modules 17 Digital Outputs 18 Technical Description 18 Technical Specific...

Page 4: ...house Telephone Systems 28 Set up for Limited Communication Speed 29 Troubleshooting 29 TCP IP Dial Up via TCP IP Modem XM500 29 GSM Communication Europe only 29 M20T Safety Precautions 29 Required T...

Page 5: ...personnel If the unit is modified in any way except by the manu facturer all warranties concerning operation and safety are invalidated Make sure that certain local standards and regulations are obse...

Page 6: ...sories Version Overview Housing With Man Machine Interface MMI Without MMI Application Module Standalone EPROM Standalone Flash EPROM C Bus Flash EPROM C Bus serial port for Meter Bus Flash EPROM LONW...

Page 7: ...DULE 2 83 in 72 mm 3 94 in 100 mm APPLICATION MODULE C BUS PORT SERIAL PORT STANDARD DIN CUTOUT FAST ACCESS KEYS BASIC FUNCTION KEYS LCD DISPLAY 1 34 in 34 mm 1 34 in 34 mm 3 34 in 85 mm 3 34 in 85 mm...

Page 8: ...ps No Inside cabinet DIN rail DIN rail Mounting clips The DIN rail mounting clips are part of the delivery The Accessory kit XL 50 ACC3 for front door mounting must be ordered separately Housing Front...

Page 9: ...Fig 12 Fig 12 Fixing controller with front door mounting clamps Inside Cabinet without MMI 1 Break plastic tabs covering the slots on the controller for the DIN rail mounting clips using a screwdriver...

Page 10: ...re 4 Optional Connect the C Bus to the application module as described in chapter C Bus Connection Procedure and or connect the application module serial port to the Meter Bus adapter as described in...

Page 11: ...ions from the chapter Phoenix Terminal Block Installation Procedure Fig 16 Wiring options The two screw terminal blocks are attached directly to the controller housing The Phoenix terminal blocks are...

Page 12: ...32 33 34 A01 A02 A03 A04 DI1 DI2 DI3 DI4 AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8 AGND GND 00000044 10V 5mA REF DI POWER Fig 20 Phoenix Terminal Block B IMPORTANT The numbering of the Phoenix terminals differ...

Page 13: ...ightning protection Cable Lengths and Cross Sectional Areas Table 6 Signal types and cross sectional areas Cross sectional area Type of signal 300 ft 100 m 550 ft 170 m 1 300 ft 400 m Power supply 24...

Page 14: ...Vdc If any input is sourced with more than 40 Vdc or negative voltage the other inputs will be influenced This could result in wrong values Sensors and Transducers AGND 00000061 31 33 35 37 39 41 43 4...

Page 15: ...tage For long cable distances the analog input signal may be sensitive to interference In this case an external relay may also be used for normally closed contacts Firmware Release 2 04 xx L N AGND 00...

Page 16: ...nd overvoltage up to 24 Vac and 40 Vdc Parameter requirements If the digital inputs are used for normal digital or analog signals the signals have to meet the static and dynamic requirements stated in...

Page 17: ...nnection examples for the relay modules MCD 3 and MCE 3 are shown here IMPORTANT The external supply of the relay modules must be 24 Vac the same as of the supply of the controllers The analog outputs...

Page 18: ...tal output is short circuited the fuse will be blown and will interrupt the main power In that case the con troller does not work If the CPU is running into the WATCHDOG caused by a software or hardwa...

Page 19: ...rview of CRT Series AC DC current Transformer max AC current max DC current CRT 2 2 A 0 5 A 500 mA CRT 6 6 A 1 3 A 1300 mA CRT 12 12 A 2 5 A 2500 mA Fig 34 AC DC current graphs 1450 Series All transfo...

Page 20: ...tuators etc to the digital output terminals 9 Select one of the transformers of the CRT series or 1450 series from the Table 13 or Table 14 or take a commercially available standard transformer fulfil...

Page 21: ...the transformers listed in chapter Power Supply page 15 b Connect the chosen transformer directly to the actuator or sensor 7 Connect sensors transducers etc to the digital input terminals 8 Connect v...

Page 22: ...with MMI 1 Unplug the screw terminal block B or Flat Strip cable to Port B while the controller is connected to the power supply 2 Adjust the display contrast with a slotted screwdriver or a cross tip...

Page 23: ...D RESERVED C BUS TERMINATION SWITCH 0000060c 4 5 6 Fig 43 C Bus connection and LEDs Up to 30 controllers can communicate with one another and the Excel Building Supervisor PC XBS via the C Bus Instead...

Page 24: ...0 m For the US the repeater is available either with or without housing In Europe only the version with housing is allowed Table 19 Ordering No for Repeaters Description US Ordering No European Orderi...

Page 25: ...9D220150 non plenum The FTT specification includes two components that must be met for proper system operation The distance from each transceiver to all other transceivers and to the termination must...

Page 26: ...t contexts Again this list is not exhaustive and therefore does not provide explanations for every possible service LED behavior Table 22 LONWORKS Service LED behavior descriptions Behavior Context Li...

Page 27: ...pecifications MMI type Cable Length XI582 remote MMI XW 582 17 ft 5 m XI584 PC based MMI XW 585 17ft 5 m For connection to the XI584 a standard null modem cable may be used Fig 50 MMI Cable details Mo...

Page 28: ...ction The Excel 50 Controller will automatically detect whether the modem ISDN terminal adapter is initialized in auto answer or manual answer mode and it will set the modem to the manual answer mode...

Page 29: ...6 Kbaud Due to a special transmission mechanism the effective communication throughput is lower than 9 6 Kbaud however this will be noticeable only when high data volumes are transmitted e g when app...

Page 30: ...Serial Cable For connecting the M20T to the Excel controller a standard RS232 cable 9 pin V24 sub D sockets is required GSM Antenna Requirements All major suppliers of GSM antennas can supply GSM900 A...

Page 31: ...ximately 3 meters there should not be any vertical barriers that would block the antenna signal such as doors PCs cupboards etc Select the most suitable antenna Location and mounting limitations may r...

Page 32: ...otherwise its call will not be recognized by the XBS The M20T can be forced to do so by adding the letter i to the telephone number e g ATDi1234567891234 NOTE As soon as the PIN is entered into the E...

Page 33: ...he underside of the PW3 and pry downward to loosen clamp until the unit snaps onto the rail See Fig 57 0000108a 1 2 3 DIN RAIL Fig 57 Mounting of PW3 2 Connect Meter Bus devices to PW3 Meter Bus Adapt...

Page 34: ...ast X X X X X X 300 2400 1 normal X X X X X X X Schlumberger CF50 300 2400 2 ref day X Landis Staefa Sonogyr WSD 300 1 X X X X X X X X Techem Delta tech Kompact and Split 300 2400 1 X X X X X X ABB SV...

Page 35: ...e value previously displayed will be restored If Time is selected Set the time using the or keys Use the arrow keys to move from field to field Confirm with ENTER Use the CANCEL key to return to the p...

Page 36: ...d Set the controller number using the or keys Confirm with ENTER IMPORTANT If no controller number is set or if the number shown is not reconfirmed the controller will not go online on the C Bus after...

Page 37: ...of Remote Trend Buffer Entries is 104 If a new value for Appl Mem Size has not been entered the cursor is at NEXT Confirm with ENTER and continue to the next screen To increase the size of the buffer...

Page 38: ...il you have reached the configuration screen again Codes which are not allowed have the value 1 instead of the previously entered code Change the codes until all codes are correct You will now come to...

Page 39: ...NTER to select the value Change the value using the or keys Confirm with ENTER In the case of digital points the following screen is displayed user addr STATE VALUE 0 Press ENTER to select the value C...

Page 40: ...ll Inc Honeywell Limited Honeywell Limitee Honeywell AG Honeywell Plaza 155 Gordon Baker Road B blinger Stra e 17 Manufacturing P O Box 524 North York Ontario D 71101 Sch naich location certified to M...

Reviews: