background image

Echoflex Installation Guide

Dual Tech Ceiling-mount Vacancy Sensor

Prepare for Installation

Ceiling-mount sensors are intended for installation to a finished ceiling
surface, soft ceiling tile mounted, or attached to a round or octagonal fixture
junction box.

Compliance

UL/cUL listed, complies with UL508A, UL916, and CSA C22.2 No. 14

CE compliant

For use with Echoflex dimming and relay products.

Environment

Ambient

For indoor, commercial controls use only. Indoor installation only. The sensor
operates in ambient temperatures of -10°C to 40°C, with a maximum of
90% non-condensing humidity.

Installation

Echoflex recommends paying special attention to the installation
environment:

When operating in PIR only modes, the sensor must have an
unobstructed view of the room. Do not mount behind or near tall
cabinets, shelves, hanging light fixtures, etc.

Do not install the sensor within eight feet from an HVAC airflow
duct/vent.

Install the sensor where it cannot easily sense movement in areas
outside of the intended space, such as hallways, glass partitions, or
adjacent rooms. If the installation location cannot avoid these
conditions, portions of the lens can be masked to block the sensor
view of these undesired areas. See

Lens Masking on page 10

.

Note:

In areas of increased noise activity, enabling PIR only mode may

allow for better occupancy detection results. See

DIP Switch Settings on

page 7

.

Dual Tech Ceiling-mount Vacancy Sensor

Page 2 of 12

Echoflex Solutions, Inc.

Summary of Contents for Elaho Dual Tech Ceiling-mount Occupancy Sensor

Page 1: ...ctionality upon detection of vacancy The ceiling mount sensor offers 360 degree coverage with optimized lens options to accommodate small and large spaces The sensor is available in a white or black finish Small Room Lens coverage 452 ft 2 at 8 ft 42 m 2 at 2 4 m 804 ft 2 at 10 ft 74 3 m2 at 3 m Large Room Lens coverage 1 809 ft 2 at 8 ft 168 m 2 at 2 4 m 3 019 ft 2 at 10 ft 280 m 2 at 3 m Field i...

Page 2: ...ial attention to the installation environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixtures etc Do not install the sensor within eight feet from an HVAC airflow duct vent Install the sensor where it cannot easily sense movement in areas outside of the intended space such as hallways gl...

Page 3: ... devices be grounded for ESD protection Pull an additional 14 AWG 2 5 mm2 wire for grounding when control wires are not installed in grounded metal conduit Note When using Category 5 or equivalent cable on the EchoConnect communication bus please note the following Cat5 wiring must be terminated using EchoConnect Cat5 Termination Kit and must be installed using a bus topology Refer to the installa...

Page 4: ... location junction box or finished surface and strip each wire 3 8 9 10 mm 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sensor in one hand while gently twisting the cover clockwise 3 Connect the EchoConnect wires from the sensor to the installed wires a Connect the data typically black EchoConnect wire from sensor to the inco...

Page 5: ... hole for wire pass through b Remove the ceiling tile material from marked access hole c Pull the sensor wires through the access hole 4 Insert the soft ceiling tile adapters through the provided pinholes in the sensor mounting plate one set located on each side of the sensor near the mounting keyholes Push the adapters through the ceiling tiles then bend each tine over in opposite directions for ...

Page 6: ...unctionality on the Dual Tech Ceiling mount Vacancy Sensor DIP switches Space and Address switches Set Space and Address Two rotary switches on the controller provide for assignment of the sensor Space and Address By default these switches are set to Space 1 Address 1 Commands are shared by all devices within a given space 1 Set the Space rotary switch to the desired number 1 through 16 for the sp...

Page 7: ...re ignored Instead the settings made by the EchoAccess Mobile App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On and Switch 4 is Off Auto Both switches are On 5 Detection LEDs When set to On default the occupancy detection LEDs illuminate when movement is detected When set to Off the occupancy detection LEDs a...

Page 8: ...meout When the vacancy timeout in the space has only been reset by acoustic detection for 60 minutes acoustic detection is disabled until the next PIR detection event PIR only Detection When acoustic detection is disabled DIP switch 6 set to On the following logic is used When the space is vacant only manual control can switch the state to occupied When the space is occupied PIR detection and manu...

Page 9: ...ns If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period after a vacancy timeout occurs During this grace period if the sensor detects occupancy it will turn on or restore the previous lighting condition Auto Vacancy Timeout The Auto vacancy timeout setting va...

Page 10: ...n seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detection is enabled any sound detected will illuminate the lens green 4 Adjust the lens masking if installed blocking certain areas of the installed space from sensor detection See Lens Masking below 5 Wa...

Page 11: ...m 10 ft 3 0 m 10 ft 4 6 m 15 ft 4 6 m 15 ft 6 1 m 20 ft 6 1 m 20 ft 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft Dual Tech Ceiling mount Vacancy Sensor Page 11 of 12 Echoflex Solutions Inc ...

Page 12: ...Echoflex Installation Guide Dual Tech Ceiling mount Vacancy Sensor Dual Tech Ceiling mount Vacancy Sensor Page 12 of 12 Echoflex Solutions Inc ...

Reviews: