ElahoAccess Interface
2.
Connect Interface ESD ground wire pigtail.
a.
Strip 7/16” (11 mm) of insulation from the ends of the Interface
ground wire pigtail, provided in the termination kit, and the
incoming ground wire.
b.
Use one WAGO 221 Series LEVER-NUTS
®
, provided in the
termination kit, to connect the Interface ESD ground pigtail and
the incoming ground. For Interfaces using grounded metal
conduit, connect the ground pigtail to the metal back box ground
location.
c.
Install the ESD ground wire pigtail FASTON connector to the
mating receptacle on the Interface electronics.
3.
Terminate EchoConnect wires. EchoConnect is topology free, you may
install the wires in any combination of bus, star, loop, or home-run.
a.
Strip 7/16” (11 mm) from the ends of each EchoConnect power
pigtail wire (black and white wire pair), provided in the
termination kit, and the installed control wires.
b.
Use the WAGO connectors provided to connect the EchoConnect
pigtail wires and the installed Belden 8471 control wires. One
WAGO should be used for the white wire pair (data +) and one
for the black wire pair (data -). Open the terminal levers on the
WAGO connector and insert the installed Belden 8471 wire and
the lead from the power pigtail into the terminals then close the
levers.
c.
Install the two pin connector from the EchoConnect pigtail to the
mating receptacle on the station electronics.
4.
Terminate power supply wiring (24 VDC Auxiliary) wiring.
a.
Strip 7/16” (11 mm) from the ends of each Auxiliary power
pigtail wire (black and red wire pair), provided in the termination
kit, and the installed power wires.
b.
Use the WAGO connectors provided to connect the Auxiliary
pigtail wires and the power wires. One WAGO should be used
for the red wire pair (p) and one for the black wire pair
(negative -). Open the terminal levers on the WAGO connector
and insert the installed wire and the lead from the power pigtail
into the terminals then close the levers.
c.
Install the two pin connector from the EchoConnect pigtail to the
mating receptacle on the station electronics.