background image

Echoflex Installation Guide

Access Interface

EchoConnect

The Interface connects to the EchoConnect station communication bus.
EchoConnect is a bi-directional protocol that uses one pair of wires
(data + and data -) for both data and power. Echoflex recommends using
Belden 8471 Class 2 wire (or approved equal – see the Echoflex cable
cross database

echoflexsolutions.com/files/Elaho_Data_Cable_Wire_

Specs

for equal alternatives). The total combined length of an

EchoConnect wire run using Belden 8471 may not exceed 500 m
(1,640 ft), with a maximum distance of 400 m (1,312 ft) between any two
devices.

Note:

All control wiring should be installed and terminated by a

qualified installer and should follow standard wiring installation
practices. Leave approximately 25.4 cm (10 in) of wiring in the
back box for connection and to allow slack for future service
needs.

Note:

Echoflex requires that all stations and devices be grounded

for ESD protection. Pull an additional 2.5 mm

2

(14 AWG) wire for

grounding when control wires are not installed in grounded metal
conduit.

Prepare for installation

The ElahoAccess Interface ships with the electronics, wall plate, and
wire termination kits including wire pigtails for 24 VDC auxiliary
power and EchoConnect.

The station may be installed into an industry-standard flush-mount back
box (RACO 690 or equivalent provided by others) or surface-mount back
box (sold separately and available from Echoflex).

Installation

The back box must be installed plumb and square for best results. Ensure
the back box is clean and free of obstructions and that all wiring is
installed correctly.

Locate the wire termination supplies included with the packaging.

Access Interface

Page 2 of 8

Echoflex

Summary of Contents for ElahoAccess

Page 1: ...figure and control your Elaho Presets Spaces Zones and devices Specification Installation Environment For indoor commercial controls use only Echoflex recommends paying special attention to the instal...

Page 2: ...25 4 cm 10 in of wiring in the back box for connection and to allow slack for future service needs Note Echoflex requires that all stations and devices be grounded for ESD protection Pull an additiona...

Page 3: ...he mating receptacle on the Interface electronics 3 Terminate EchoConnect wires EchoConnect is topology free you may install the wires in any combination of bus star loop or home run a Strip 11 mm 0 4...

Page 4: ...ed to connect the Auxiliary pigtail wires and the power wires One WAGO should be used for the red wire pair V and one for the black wire pair V Open the terminal levers on the WAGO connector and inser...

Page 5: ...ng the mounting screws provided If using spacers insert the screws through the spacers as well Interface LEDs Power The top blue LED lights when the device has power Bluetooth The bottom yellow LED li...

Page 6: ...cure Note If you are installing a multi gang wall plate and the stations are misaligned in the mounting box the wall play will not attach properly Loosen the screws that secure the station to the back...

Page 7: ...e of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that...

Page 8: ...own expense This device contains a wireless module with the following identification numbers FCC ID T9JRN4020 ISED Compliance This device contains a license exempt transmitter receiver that complies...

Reviews: