7
Power Up and Test
1. Restore power to the circuit. The dimmer will turn on to full output.
2. Test the circuit by linking a wireless switch (If factory pre-commissioning has been
ordered a switch may be linked before delivery). To link a switch:
a. Within radio range of the controller, press the switch paddle up (On) three times
consecutively.
b. Press the paddle down (Off) three times consecutively.
c. Press the paddle up again, three times consecutively.
3. Test the controller response.
a. Press the switch down (Off) once. The controlled lighting should respond by
dimming off.
b. Press the switch up (On) once. The controlled lighting should respond by
dimming on.
Note: The linking method described in “Step 2” will link the switch to any controllers
that are within radio range that do not already have switches or sensors linked to
them.
4. Press and hold the paddle down or up switch to manually dim the circuit down or
up.
Diagnostic LED’s and buttons
LEARN button
The LEARN button is used to link switches or sensors to the controller.
1. Press the button marked LEARN for a half second. In link mode the LEARN LED will
stay ON and the POWER LED will toggle every 2 second.
2. Using the switch that will be linked to the controller, press the wall switch ON three
times. If linking a sensor, press the sensors TEACH or LINK button, refer to the sensor
documentation. The POWER LED will remain lit for 4 seconds while it links the new
device. It will resume toggling allowing you to link another device up to a total of 20
devices.
NOTE:
Linking a switch or sensor that is already linked to a controller, will
remove or unlink it from the controller.
3. To exit link mode, press the LEARN button on the controller again for a half second.
Link mode will also time out after no activity in 30 seconds.
CLEAR button
The CLEAR button erases all devices linked to the controller and resets the controller to
factory default settings.
1. Press the CLEAR button (approximately 5 seconds) until the green LEARN LED blinks
on.
LED Blink Codes and Operation
The table below describes the LED activity & associated mode of the controller.
Description
Learn LED
Power LED
Relay
LINK mode
ON
Toggle 2 sec.
Toggle
Storing ID
ON
ON 4 sec.
ON 4 seconds
Clearing ID
ON
OFF 4 sec.
OFF 4 seconds
CLEAR mode
ON 1 sec.
N/A
ON 1 sec.