background image

Echoflex Installation Guide

Photo & CCT Sensors

Installation

The sensor should be installed in a location where it has direct exposure
to a window or skylight. For example, mount the sensor on the ceiling,
aligned with a window about 1.2 m (4 ft) away.

The sensor can be attached to most surfaces; suspended ceiling tile,
finished wallboard, or other surfaces using a flexible adhesive.

Note:

A concrete or metal mounting surface can limit radio

communication. Create some separation by mounting the sensor
first on non-metalic material, e.g., 1/2-inch plywood.

The location and position of the sensor directly affects the quality of
messages received by the linked controller. Determine the installation
method and follow the instructions.

Note:

Consider linking the TAP-31 TAP-41 while you have access

and before replacing the cover. See

Link to a Controller on the

facing page

.

Wire Staples to Ceiling Tile

1. Use your fingers to remove the sensor's cover, flexing it gently to

release the tabs that hold it in place. If you have difficulty, try
inserting a small flatblade screwdriver under one of the release tabs.

2. Mark the sensor mounting location on the ceiling tile.
3. Remove the ceiling tile from the T-bar frame.

Pinholes

Keyhole

4. Insert the wire staples (provided)

through the pinholes on the sensor,
one set located on each side near the
keyholes.

5. Poke the tines through the ceiling tile,

then bend each tine over in opposite
directions for a secure fit.

6. Replace the ceiling tile and reattach

the sensor cover.

Wallboard Ceiling

1. Use your fingers to remove the sensor's cover, flexing it gently to

release the tabs that hold it in place. If you have difficulty, try
inserting a small flatblade screwdriver under one of the release tabs.

2. Mark the location of the keyholes on the ceiling.
3. Bore two holes and insert screw anchors (not provided).
4. Attach the sensor to the ceiling with screws (not provided).
5. Replace the sensor cover.

Photo & CCT Sensors

Page 2 of 8

Echoflex

Summary of Contents for TAP-31

Page 1: ...oor values or predefined color temperature values The sensor supports four equipment profile settings that monitor exterior light levels up to 100 000 lux 9 290 fc and a color temperature range of 2 0...

Page 2: ...Ceiling Tile 1 Use your fingers to remove the sensor s cover flexing it gently to release the tabs that hold it in place If you have difficulty try inserting a small flatblade screwdriver under one of...

Page 3: ...rn button on the controller to activate Link mode If necessary refer to the controller product documentation 3 Press the Teach button on the sensor once to send a link message An LED blinks to confirm...

Page 4: ...6 64 seconds 10 minutes 100 9 3 32 seconds 320 seconds 100 9 3 16 seconds 160 seconds For the sensor to send an on change message it needs sufficient power Stored energy above 3 5 V or Ambient light l...

Page 5: ...confirms a good installation location 1 Press and hold the Teach button until the green LED is displayed Release the button to enter the menu and display the first item the blinking green LED 2 Press...

Page 6: ...o 80 dBm good Red 80 to 95 dBm poor move closer No LED No linked controllers detected The test repeats every five seconds and runs for 50 seconds To exit before the time out press and hold the Teach b...

Page 7: ...utton until the LEDs stop blinking to select EEP Select The blue and green LEDs blink code displays the current setting 4 Press and release the Teach button to navigate the options Indication Setting...

Page 8: ...ons Any modifications or changes to this product not expressly approved by Electronic Theatre Controls Inc could void the user s authority to operate the product Operation of this equipment in a resid...