background image

Echoflex Installation Guide

Photo & CCT Sensors

Range Confirmation

The Range Confirmation test quantifies the strength of the wireless signal
to a linked controller that has range confirmation capability.

Note:

Only one controller can be linked to the TAP-31 TAP-41 to

run the test properly. Disable repeaters that are in range.

1. Press and hold the

[Teach]

button until the green LED is displayed.

Release the button to enter the menu and display the first item, the
blinking green LED.

2. Press and release the

[Teach]

button to cycle through the menu of

color LEDs and stop when the blue LED is blinking.

3. Press and hold the

[Teach]

button until the LED stops blinking to

initiate the Range Confirmation test.

After the TAP-31 TAP-41 transmits and receives a Range
Confirmation message, the signal strength status is displayed as an
LED blink color.

LED Blink

Signal Strength

Green

-41 to -70 dBm (best)

Blue

-70 to -80 dBm (good)

Red

-80 to -95 dBm (poor, move closer)

No LED

No linked controllers detected

The test repeats every five seconds and runs for 50 seconds. To exit
before the time-out, press and hold the

[Teach]

button.

Rapid Response Test

The Rapid Response Test confirms the settings on powered controllers to
which the TAP-31 TAP-41 is linked. The test accelerates the sensor's
message rate, making the controller respond to light level changes faster.
The transmission rate is increased to every 16 seconds for 100 seconds
and then returns to normal operation.

1. Press and hold the

[Teach]

button until the green LED is displayed.

Release the button to enter the menu and display the first item, the
blinking green LED.

2. Press and release the

[Teach]

button to cycle through the menu of

color LEDs and stop when the red LED is blinking.

3. Press and hold the

[Teach]

button to initiate the Rapid Response Test.

4. Vary the light level on the sensor to test the dimming and recovery

response of the connected light fixture.

5. To exit before time-out, press and hold the

[Teach]

button.

Photo & CCT Sensors

Page 6 of 8

Echoflex

Summary of Contents for TAP-31

Page 1: ...oor values or predefined color temperature values The sensor supports four equipment profile settings that monitor exterior light levels up to 100 000 lux 9 290 fc and a color temperature range of 2 0...

Page 2: ...Ceiling Tile 1 Use your fingers to remove the sensor s cover flexing it gently to release the tabs that hold it in place If you have difficulty try inserting a small flatblade screwdriver under one of...

Page 3: ...rn button on the controller to activate Link mode If necessary refer to the controller product documentation 3 Press the Teach button on the sensor once to send a link message An LED blinks to confirm...

Page 4: ...6 64 seconds 10 minutes 100 9 3 32 seconds 320 seconds 100 9 3 16 seconds 160 seconds For the sensor to send an on change message it needs sufficient power Stored energy above 3 5 V or Ambient light l...

Page 5: ...confirms a good installation location 1 Press and hold the Teach button until the green LED is displayed Release the button to enter the menu and display the first item the blinking green LED 2 Press...

Page 6: ...o 80 dBm good Red 80 to 95 dBm poor move closer No LED No linked controllers detected The test repeats every five seconds and runs for 50 seconds To exit before the time out press and hold the Teach b...

Page 7: ...utton until the LEDs stop blinking to select EEP Select The blue and green LEDs blink code displays the current setting 4 Press and release the Teach button to navigate the options Indication Setting...

Page 8: ...ons Any modifications or changes to this product not expressly approved by Electronic Theatre Controls Inc could void the user s authority to operate the product Operation of this equipment in a resid...