MN300820 Rev B4
29
|
Configuration
(with Display…Continued)
Step
Four
STEP 3 - SETTING THE HEIGHT (SENSOR HEIGHT)
1. In TOP-LEVEL MENU mode, select
TANK
.
2. Select
HEIGHT
.
3. Using the UP and DOWN buttons, set the
HEIGHT
of
the tank (transducer face to the bottom of the tank).
4. To enter the value, press and hold OK for 2 seconds and
release.
SAVED
will display.
5. Select
EXIT
to return to TOP-LEVEL MENU.
Note: The HEIGHT setting also determines the 4 mA current location. To reverse the current output with
20mA at the bottom of the tank, use the REV MA function.
Note: To speed up the scrolling of the values on the display, hold down the OK button while holding down the
UP or DOWN buttons.