960E
Installation Manual
ECI Telecom Ltd. Proprietary
12
4. System
Mounting
4.1. Shelf
Installation
4.1.1. Remove
Door
Prior to installing the shelf, the door must be removed.
¾
To remove the door:
1. Unscrew the 2 retaining bolts on the bottom front side.
2. Gently lift the door up and pull it towards you.
4.2. Mounting
Methods
The 960E can be mounted in the following racks:
•
19" (482 mm);
•
23" (584 mm);
•
ETSI (535 mm).
Figure 7, presents the installation of rack mounting brackets for ETSI (the installation
of rack mounting brackets for 19" and 23" racks are similar). The rack mounting
brackets for ETSI racks can be inversed and uses for 19" racks.
4.2.1. Rack
Installation
Â
Note:
Two technicians are recommended to mount the 960E in the rack to
properly position and attach the rack
Â
Note:
The recommended minimum distances between shelves to allow proper
air circulation and cable bending clearance are:
•
Top and Bottom — 10 cm clearance between shelves
•
Right and Left — 0 cm between shelves
¾
To install the 960E shelf in a rack or cabinet:
1. Lift the shelf onto the rack: then align the shelf such that the top and bottom holes
on each side of the shelf are aligned with the holes in the rack.
2. Use M6 screws in the top and bottom holes on each side of the shelf to secure the
shelf in the rack.