Installation and Startup of CI 3000 / SIOX
50
Version 2.09 09. April 2014
5.10 Firmware update
New firmware is loaded to the CI 3000 Store Computer by running the Update
CI3000 Vx.xx.exe
program on a PC
connected to the MODEM port of the CI 3000 Store Computer by null modem cable (EAG No. PCZKABSER2).
Operating systems supported are: Windows 2000 / XP / Vista / 7.
Damage to equipment and goods! Before
the firmware update the affected component, i.e. equip
ment must be brought into a safe state as the deactivation of the controller during the firmware update
can have undesired effects on the component, i.e. equipment.
Danger data loss!
The loading of software via firmware update must not be interrupted. The power
cable and the null modem cable must not be disconnected during the firmware update. It must be en
sured that power is supplied throughout the entire procedure. An interruption of the firmware update
can result in an inoperative controller.
Danger of a loss of the configuration!
Due to more fundamental changes to the Store Computer,
1. During the update from version < 5.0 to version 5.0 and higher it is necessary to re-enter all settings
for the error message transmission, see menu 6-1-4 and all sub-menus.
E.g.
2. During an update from version 1.x to version 2.x and higher no configuration data (in particular for
error message transmission) is transferred!
First start initiated if update from Version 1.x to Version 2.x or higher is detected when starting the
Store Computer results in these configurations being deleted! With future updates to
Versions 2.0 and higher, fault report transmission configurations are preserved on first start.
Summary of Contents for CI 3000
Page 20: ...Application of CI 3000 14 Version 2 09 09 April 2014 Notice...
Page 62: ...Installation and Startup of CI 3000 SIOX 56 Version 2 09 09 April 2014 Notice...
Page 118: ...Menu structure of CI 3000 112 Version 2 09 09 April 2014 Notice...
Page 120: ...Decommissioning and disposal 114 Version 2 09 09 April 2014 Notice...
Page 126: ...Alarms and Messages of CI 3000 120 Version 2 09 09 April 2014 Notice...