Firmware V6.6.9
29.07.2020
102/147
Note: GLT = Building Control System and DDC = Digital Direct Control
Menu 4-1-2 - Signal Inputs
This button is used to call up the list of the digital alarm and signal inputs of the system centre. All
important parameters and the status of the inputs are displayed there. Alarm and signal inputs can be added
using the "New entry" button. Already added digital inputs can be selected and configured using the
corresponding screen or deleted again. See chapter 4.2.1 for details.
The screen contains the following parameters:
Signal input
Eingabe
Vorgabe
Message text
Freely editable message text of the digital input
max. 19 characters
-
Priority XX
Priority of the signal / alarm input
0..99
0
Delay time [Min.] XX
Delay time of the signal / alarm in minutes
0..255
1
Quiescent current (low-active) X
Alarm is signalled if
- quiescent current = Yes: (signal voltage not
present, low-active)
- quiescent current = No: (signal voltage is
present, high-active)
Y/N
Y
Signal input
Module
Module
1)
to which the message / alarm signal is
connected
SIOX1 ..SIOX4
-
Submodule XX
Submodule
1)
to which the message / alarm
signal is applied; this is ONLY visible if
module=DDC1..DDC4 has been selected
1..4
-
Input XX
Input
1)
to which the message / alarm signal is
applied
1..12
-
Status XX
Current status of the input:
OK = light grey, no signalling
Waiting = yellow: signalling, delay time running,
Message = green: no alarm
Alarm = red: signalling, alarm / message has
been tripped
–
-
1)
Designations of the supported modules / inputs:
CI 4x00
system centre, internal inputs IN1 / IN2 (terminals A1, A2 / B1, B2)
SIOX1 1. extension module, inputs 1 .. 12
SIOX2 2. extension module, inputs 1 .. 12
SIOX3 3. extension module, inputs 1 .. 12
SIOX4 4. extension module, inputs 1 .. 12
DDC1 1. GLT DDC module 1
DDC2 2. GLT DDC module 2
DDC3 3. GLT DDC module 3
DDC4 4. GLT DDC module 4
Note: GLT = building control and. DDC = Digital Direct Control
Only those SIOX modules and GLT PLC modules are provided for selection that have been configured
accordingly in screen 4-1-1! A description of the functions can be found in chapters
.