Firmware V6.6.9
29.07.2020
104/147
SIOX3 3. extension module, inputs 1 .. 12
SIOX4 4. extension module, inputs 1 .. 12
DDC1 1. GLT DDC module 1
DDC2 2. GLT DDC module 2
DDC3 3. GLT DDC module 3
DDC4 4. GLT DDC module 4
Note: GLT = building control and. DDC = Digital Direct Control
Menu 4-1-4 - Week Timers
The entry screen for configuration of the week timers of the system centre is called using this
button. All important parameters and the status of the week timers are displayed there. Week timers can be
added using the "New entry" button. Already added inputs can be selected and configured using the
corresponding screen or deleted again.
Every week timer functions as independent week timer with up to 7 control times to which a switching output
and/or a passing contact can be assigned. The output is then active if the current time is within any of the 7
configured control times.
The screen contains the following parameters:
Week timers
Input
Default
Name
Freely editable name / designation of the
week timer
max. 32 characters
-
Control times
Start
Week timer start
00:00..23:59
08:00
End
Week timer end
00:00..23:59
4:00 PM
XXXXXXXXX
Weekdays and groups of days
Mon-Fri
Mon-Sat
Mon-Sun
Sat-Sun
Mon, Tue, Wed,
Thu, Fri, Sat, Sun
Mo-Fr
Switching contact and/or
passing contact
1)
Module
Module
1)
to which the output is connected
SIOX1 ..SIOX4
-
Submodule XX
Submodule
1)
to which the output is
connected; this is
ONLY visible if module=DDC1..DDC4 has
been selected
1..4
-
Output XX
Output
1)
to which the output is connected
1..12
-
Status XX
Current status of the output:
Not active: = light grey
Active= green
-
-
Only those SIOX modules and GLT PLC modules are provided for selection that have been configured
accordingly in screen 4-1-1! A description of the functions can be found in chapter