Example: Procedure for configuration using the LDSWin PC software
Specify alarm destinations
The refrigeration pack system should notify the service centre and the building control system should notify
the caretaker.
Specify the priorities and priority groups and assign them to the alarm destinations
Refrigeration pack system: Priorities 0..9Entire installation / building control systems: Priorities 10..99
Set the priorities in the components accordingly
The meaning of the priorities X1 and X2 in combination with the alarm relay must be observed, see chapter
: components / controller of the refrigeration pack system signal with the priorities 0..9
components of the building automation (heating, air conditioning,..) with the priorities 10..99
In order to illustrate the priority concept and the decades (priority groups), these are listed in the following table
and explained using examples:
Vertical
Maintenance-group-
dependent allocation
of alarm priorities X0..X9
in decades (priority groups)
Refrigeration pack system
X0
Heating
X1
Air conditioning
X2
...
…
X9
Horizontal
Logical classification of alarms and
messages for each alarm number.
The alarm priorities listed on the left
are
0
1
0
2
0
...
9
0
interpreted as messages-
registered in the message list
no alarm is signalled (no signal
tone is sounded, buzzer)
1
2
1
1
1
2
2
1
2
2
...
9
1
9
2
interpreted as alarm
registered in the alarm and
message lists
alarm is signalled remotely by
modem according to the
configuration of the remote
alarm signalling
alarm is signalled locally using
horn and buzzer (system centre
and operator terminal)
coupled with the two alarm
relays and "PRIO1 and PRIO2"
LEDs
3
...
9
1
3
...
1
9
2
3
...
2
9
...
9
3
...
9
9
interpreted as Alarm- registered
in the alarm and message lists
alarm is signalled remotely by
modem according to the
configuration of the remote
alarm signalling
alarm is signalled locally using
horn and buzzer (system centre
and operator terminal)
the AUX relay is actuated
depending on the configuration
The settings must be planned and entered carefully. In the event of incorrect configuration, there is
potential for alarms to be sent to the wrong alarm destinations and not given the required attention
there.