5.3.4 Archiving operating data
5.3.4.1 Temperature recording to EU Regulation 37/2005
Local temperature recording
Temperature is recorded at 15-minute intervals in the internal flash memory. Data is archived for 112 days. All
temperatures of the 10 sensors and the "Alarm" and "Cooling" statuses are archived. The recorded data can be
read out on the local BT 300x Operator Interface under Archive (Menu 5). Data readout on a PC is made via the
CI 320 interface. A TTY converter (available as accessory) is required for readout on a PC, see the LDSWin
operating instruction.
Temperature recording in the system centre / store computer via CAN bus
The UA 410 L records the temperature every 15 minutes and sends this for archiving via the CAN bus to the
system centre / store computer.. Data is archived for one year.
Only
the temperature values of the sensors of
the temperature zones
Rx.1 and Rx.2
and their “Alarm” and “Cooling” statuses are stored at intervals of 15
minutes for one year in the system centre / store computer via CAN bus.
If the controller is connected to the CAN bus,
only
the sensors
Rx.1 and Rx.2
in the system centre /
store computer are archived. This archiving can cover a full year.