Firmware V3.00
05.08.2019
40/100
Controller type DIP Switch S3 (Coding Switch positions 1 to 9)
1
2
3
4
5
6
7
8
9
UA 410 L
OFF OFF OFF OFF OFF OFF OFF OFF ON
Only part of the overall functions and parameters contained in the case controller are available when selecting
a specific controller type.
6.3 Terminal assignment for 230 V AC power supply
The power supply cable is connected to the case controller using the right hand terminal block PE/L/N:
The case controller can now be supplied with power. If power is being received the active lamp (LIFE LED)
flashes for approximately 10 seconds following actuation. If the case controller is also connected to the CAN
bus, then the CAN bus LED flashes. For more details on the status LEDs see chapter
Operation of the controller with a unsupported DIP switch setting is not allowed. In the case of any
setting of coding switch combinations that are not present in the list, UA 410 L is automatically applied
as controller type and an alarm signal is created. In the event of change of the controller type, all
parameters are reset to their factory settings.
Warning - hazardous electrical voltage!
Danger of electric shock! BEFORE and
AFTER
connection it must checked that the 230 V AC
supply cable is
off load
!