Firmware V3.00
05.08.2019
43/100
3. Basic configuration of the controller
- select refrigeration point (Menu 6-1)
The menus shown below only provide the overview; the display can be different for certain controller types.
Details are described in the "
" chapter.
6 Configuration - 1 Refrigeration Point
REFR. PT. POS: XXX
Refr. Pt. Name: XXXXXX
Check name of refrigeration point (can only be edited on System Centre /
Store Computer / Operator Terminal, see chapter
Item ID: XXXXX
Check Item ID of refrigeration point (can only be edited on System Centre /
Store Computer / Operator Terminal, see chapter
Priority: X
Alarm priority 0 .. 2 (See notes in Section
Sensor Fault 0m
Time to elapse before sensor break is reported.
No. Sensors X
Number of sensors. The number of sensors connected is scanned on exiting
the parameter by pressing ENTER.
4. Exiting configuration and calling "Defrost Timer":
Press the
ESC
key twice to exit Menu 1 Configuration and
select
menu 3 Clock - 2 Defrost Timer:
3 Clock - 2 Defrost Timer
DEFR:TIMER POS: XXX
Safe Defr Time 60m
Safe defrost time; defrost duration does not extend beyond this time
Defr. 1 DD-DD hh:mm
Enter defrost times
Defr. 2 DD-DD hh:mm
...
Defr. 14 DD-DD hh:mm
5. Exit Defrost Timer:
Exit from the menu
2 Defrost Timer
by tapping the
ESC
button twice.
6. Menu 6 Configuration - select 2 Select Controller
6 Configuration - 2 Controller
CONTROLLER POS: XXX
1 Type and Version
Type, serial number and master-slave (ON/OFF)
2 Sensor Type
Select temperature sensor type
Risk of failure of the alarm signals!
An alarm is signalled if the alarm priority is set to 1..2.
No alarm is triggered if the alarm priority is set to 0; only an entry is made in the message list.
No alarm is signalled if the alarm priority is set to "--"!
* Any naming of the controller with a BT 300 x operator interface is only possible for the UA 410 L
controller.