Firmware V3.00
05.08.2019
17/100
4.2 Controller type
Temperature recording controller UA 410 L Case Controller:
Controller type
Application
UA 410 L
Temperature Data Logging Controller for maximum 10 temperature sensors
(with the option of on-off control/defrosting of five independent refrigeration points for the first five sensors).
For definition of the basic control action,
only one controller type
can be set, which is set using the
DIP
switch S3
.
Special feature
: Two device generations are available. The DIP switch S3 provides a quick distinguishing
feature:
Characteristic: 9-pole DIP switch
Characteristic: 8-pole DIP switch
Only the controller type "UA 410 L" is available for the UA 410 L:
Set controller type
DIP switch S3 (switch positions of the coding switches 1 .. 9)
1
2
3
4
5
6
7
8
9
UA 410 L
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
Selection of controller type defines the controller properties and basic controller settings. The UA 410 L
Temperature Data Logging Controller can be operated by:
•
Host computer e.g. via network / modem with connection to the system centre / store computer,
•
the system centre, a store computer or an operator terminal,
•
a local operator interface BT 300 via the DISPLAY interface on the controller or
•
a notebook (PC) with the PC-software LDSWin connected via USB.
4.3 Updating firmware
The case controller is supplied with the current firmware, ready for operation. Future software versions can
be loaded into the case controller as required by means of a firmware update, and thus updated.
Operation with an unsupported DIP switch setting is not permitted. In the event of change of the
controller type, all parameters are reset to their factory settings!
Danger data loss!
In some cases a change of firmware version can lead to the loss of all the setpoints
in the case controller.
As a precaution, the settings must be backed up by saving them to the LDSWin PC software, prior to
the update. After the firmware update the backup settings can be reloaded into the controller from
LDSWin.
A software update is only to be carried out by trained staff or factory-side by the manufacturer. More