background image

4

Eclipse UV Scanner, V1, Instruction Manual 854, 10/11/2010

3. On pilot ignited burners, manually shut off the fuel

supply to the main burner. For direct spark burners,
lock the burner firing-rate at the start position.

4. Put the control in the pilot test mode (see step 2 of

Minimum Pilot Test above).

5. Start the system normally. Observe the flame signal

during spark and after the trial for ignition. Spark
interference causes the signal during the spark to differ
more than 2 VDC from the signal after the spark.

6. If spark interference is observed, try to minimize its

affect:

a. Ensure proper grounding for the ignition circuit.
b. Isolate the scanner from ground and/or remove 

the shield connection from ground.

c. Check for proper spark gap.
d. Clean, repair, or replace faulty wiring and 

connectors.

e. Separate or shield the scanner wiring from the 

ignition wiring.

f. Reverse the wires feeding the primary to the 

ignition transformer.

g. Move the location of the ignition transformer.

Pilot Flame Failure Test

1. Put the control in the pilot test mode (see step 2 of

Minimum Pilot Test above).

2. Start the system normally.

3. After the pilot has lit, manually turn off the fuel supply.

The controller should lock out of flame failure. If not,
then the controller is detecting a false flame signal.
Find the problem and correct it before resuming normal
operation.

Main Flame Failure Test

1. Put the control in the "Run" position (see step 6 of

Minimum Pilot Test above).

2. Start the system normally.

3. After the sequence lights the main flame, manually shut

off the fuel supply. If the control does not shut down in
less than 4 seconds after visually observing that the
flame extinguished, it may be detecting a false flame
signal. Find the problem and correct it before resuming
normal operation.

Process Conditions Test

1. Start the system normally.

2. Observe the flame signal as the system operates at

various firing rates under process (at temperature)
conditions.

3. Perform the Main Flame Failure Test under these

conditions and verify that the control shuts down in less
than 4 seconds after visually observing that the flame
extinguished.

Limit & Interlock Tests

Periodically check all interlock and limit switches by
manually tripping them during burner operation to make
sure they cause a system to lock out.

  Never operate a system that is improperly adjusted

or had faulty interlocks or limit switches. Always
replace faulty equipment before resuming
operation. Operating a system with defective or
bypassed safety equipment can cause explosions,
injuries, and property damage.

Maintenance

  High voltage, turn off power before disconnecting

or installing sensors or controls.

All burner systems must be maintained to ensure their
safe operation. The operator of this equipment must be
trained in safe operating procedures. The owner and
operator must set a regularly scheduled maintenance
interval based on recommendations from the equipment
manufacturers, environmental conditions, and their own
operational history. 

System Checks

Periodically test the sensors as described in "Test
Procedures".

Sensor Lens

Clean the lens regularly with a soft, damp cloth. The
presence of foreign material will measurably reduce the
flame signal strength.

Rotation

To ensure operability of stored items and to reduce the
possibility of extended down-time, periodically swap spare
sensors and control units with active ones.

WARNING

CAUTION

Reviews: