background image

1

For Ratiomatic Serial Numbers 95-5500 and Above

Version 1.01

7/97

Contents

1.0 Operating Parameters & Requirements ...............

page 2

2.0 Burner Operation & Controls ................................

page 4

3.0 Installation .............................................................

page 6

4.0 Start-Up and Adjustment ......................................

page 8

5.0 Trouble-Shooting .................................................. page 13

6.0 Maintenance .......................................................... page 14

7.0 Servicing ................................................................ page 15

The burners covered in this Guide are designed to mix fuel with air and
burn the resulting mixture. All fuel burning devices are capable of pro-
ducing explosions and fires when improperly applied, installed, adjusted,
controlled, or maintained. This Guide will provide information for using
these burners for their limited design purpose. Do not deviate from any
instructions or application limits in this Guide without written advice from
the Eclipse Combustion, Inc. Read this entire Guide before attempting to
light burners. If you do not understand any part of the information in this
Guide, contact your local Eclipse representative or Eclipse Combustion,
Inc., before proceeding further.

Important Notices About Safe Burner Operation

Store the burner inside. Exposure to the elements can damage the burner.

Adjustment, maintenance, and troubleshooting of the mechanical parts of this
unit should be done by people with good mechanical aptitude and experience
with combustion equipment.

Order replacement parts from Eclipse Combustion, Inc., only.

 Any customer-

supplied valves or switches  should carry UL, FM , CSA, and/or CGA approval where
applicable.

The best safety precaution is an alert and competent operator. Thoroughly in-
struct new operators so they demonstrate an adequate understanding of the
equipment and its operation. Regular retraining must be scheduled to maintain a
high degree of proficiency. The operator must have easy access to this Informa-
tion Guide at all times.

WARNING

Summary of Contents for RatioMatic 50

Page 1: ...e attempting to light burners If you do not understand any part of the information in this Guide contact your local Eclipse representative or Eclipse Combustion Inc before proceeding further Important...

Page 2: ...t See Figure 6 for filter element replacement Spark Plug Flame Rod Replacement Ignition plugs and flame rods wear out over long periods of normal burner opera tion For Ratiomatic burners the part numb...

Page 3: ...4 9 6 1 7 3 7 5 4 5 7 4 8 1 9 8 12 0 9 1 8 7 12 3 3 0 3 9 4 4 4 0 4 5 6 4 7 2 4 5 6 5 7 0 8 5 10 7 8 1 7 9 11 4 1 0 2 8 3 4 3 0 3 5 5 4 6 1 4 0 5 8 5 9 6 9 9 4 7 0 7 0 10 5 0 0 2 3 2 8 2 5 2 9 4 9 5 5...

Page 4: ...portionator damage Limit Controls Limit controls and safety equipment should comply with current NFPA Standard 86 and all applicable local codes and or standards NFPA Standards are available from Nati...

Page 5: ...lame Return the control motor to the low fire position Check the combustion air differential pressure as discussed in Step 2 Gas pressure drop across the burner will be too low to read reliably but th...

Page 6: ...e Trains The pilot gas valve train should be connected as close as possible to the pilot adjusting cock Flame Rod and U V Scanner See Figure 4 When mounting a UV scanner use short pipe nipples to insu...

Page 7: ...t 1 2 N P T Air Valve Shaft Tap D Air Switch Connection 1 8 N P T Blower Ignition Plug 750 1250 150000 5 1500 2000 150000 12 DETAIL Peepsight 1 2 N P T Spark Plug 1 2 N P T Flame Rod or UV Scanner 1 2...

Page 8: ...matic gas valves including the main gas butterfly and the pilot gas cock Combustion Air Blower Start the blower and check the impeller for correct rotation If it s running back wards have a qualified...

Page 9: ...matic gas valves including the main gas butterfly and the pilot gas cock Combustion Air Blower Start the blower and check the impeller for correct rotation If it s running back wards have a qualified...

Page 10: ...t 1 2 N P T Air Valve Shaft Tap D Air Switch Connection 1 8 N P T Blower Ignition Plug 750 1250 150000 5 1500 2000 150000 12 DETAIL Peepsight 1 2 N P T Spark Plug 1 2 N P T Flame Rod or UV Scanner 1 2...

Page 11: ...e Trains The pilot gas valve train should be connected as close as possible to the pilot adjusting cock Flame Rod and U V Scanner See Figure 4 When mounting a UV scanner use short pipe nipples to insu...

Page 12: ...lame Return the control motor to the low fire position Check the combustion air differential pressure as discussed in Step 2 Gas pressure drop across the burner will be too low to read reliably but th...

Page 13: ...portionator damage Limit Controls Limit controls and safety equipment should comply with current NFPA Standard 86 and all applicable local codes and or standards NFPA Standards are available from Nati...

Page 14: ...4 9 6 1 7 3 7 5 4 5 7 4 8 1 9 8 12 0 9 1 8 7 12 3 3 0 3 9 4 4 4 0 4 5 6 4 7 2 4 5 6 5 7 0 8 5 10 7 8 1 7 9 11 4 1 0 2 8 3 4 3 0 3 5 5 4 6 1 4 0 5 8 5 9 6 9 9 4 7 0 7 0 10 5 0 0 2 3 2 8 2 5 2 9 4 9 5 5...

Page 15: ...t See Figure 6 for filter element replacement Spark Plug Flame Rod Replacement Ignition plugs and flame rods wear out over long periods of normal burner opera tion For Ratiomatic burners the part numb...