background image

18

Eclipse TFB, V2, Installation Guide 310, 11/14/2014

The burner does not light or goes off 
when it cycles to high fire

Burner set too lean, becoming unstable 
as air increases.

Adjust the settings to provide more 
gas.

Insufficient pressure into ratio 
regulator.

Adjust the pressure settings on the 
main gas regulator or change spring.

Main gas adjustment valve not open 
enough.

Adjust the main gas adjustment valve.

Marginal air pressure switch setting.

Adjust the air pressure switch setting

Gas pressure switch set incorrectly.

Adjust switch setting.

The burner is erratic and does not 
respond to adjustment

Internal damage to the burner, some 
parts inside the burner are loose, dirty 
or burned out.

Contact Eclipse.

The burner is unstable and produces 
soot, smoke or excessive carbon 
monoxide

The air/gas ratio is out of adjustment. Reset the burner controls and clean 

ignition rod and UV scanner.* See 
“Adjustment, Start & Stop” section.

Bleed fitting (if used) is dirty.

Clean fitting. Check and clean filters, 
spark rod and UV scanner.* (If 
necessary).

* After this step it is important that you clean the spark rod and UV scanner, and 
make sure that there is no excessive soot on the nozzle. Clean where 
necessary.

Burner pulsates or produces noise

Acoustic feedback from tube. 

Slide a piece of steel plate over the end 
of the tube until the rumbling 
disappears. Weld the plate in place. 
Readjust the burner controls if 
necessary.

Input inconsistent with nozzle settings. Check if input is consistent with nozzle 

settings and adjust if necessary.

Too much air.

Check oxygen levels and adjust to 2% 
to 4% O

2

 (at high fire).

Burner could be improperly set to fire at 
an input rate which exceeds its 
maximum rated capacity.

Check the pressure drops to verify that 
the inputs are at the correct levels. 
Reduce the input on the air and gas as 
required to achieve the specified 
inputs.

Negative pressure in the building.

In some cases, building exhaust 
systems create a negative pressure 
that “pulls” on the exhaust outlet of the 
tube. By placing a washer or restriction 
pate over the tube outlet, this suction 
can be equalized by burner pressure.

Problem

Possible Cause

Solution

Summary of Contents for TFB030

Page 1: ...TFB030 075 TFB200 Eclipse Tube Firing Burners Models TFB030 TFB075 TFB200 Version 2 11 14 2014 Installation Guide 310...

Page 2: ...and Eclipse will not be liable for any other injury loss damage or expenses whether direct or consequential including but not limited to loss of use income or damage to material arising in connection...

Page 3: ...er Installation 9 Checklist After Installation 11 Prepare for Adjustment 11 Adjustment Start Stop 12 Adjustment Procedure 12 Step 1 Reset the System 12 Step 2 Set High Fire Air 12 Step 3 Set Low Fire...

Page 4: ...F The recommended recuperators for the TFB are the Eclipse Bayonet Data 317 and the Bayonet Ultra Spec 318 Figure 1 1 TFB Audience This manual has been written for people who are already familiar with...

Page 5: ...by sanding sawing grinding cutting and other construction activities could release crystalline silica Crystalline silica is known to cause cancer and health risks from the exposure to these chemicals...

Page 6: ...matics in the System Design section to build your system Approval of Components Limit Controls Safety Equipment All limit controls and safety equipment must comply with all applicable local codes and...

Page 7: ...tability of the electrical power Type and supply pressure of the fuel Availability of enough fresh clean combustion air Humidity altitude and temperature of air Presence of damaging corrosive gases in...

Page 8: ...e 3 4 Position the Spark Rod Flame Rod if used Table 3 2 Dimension A Inches mm for TFB075 Fuel 301k 350k 351k 400k 401k 500k 501k 600k 601k 750k Natural Gas 0 374 9 5 0 500 12 7 0 500 12 7 0 625 15 9...

Page 9: ...s that stop the spark as soon as a signal is detected may prevent establishment of flame particularly when using UV scanners The flame monitoring control must maintain the spark for a fixed time inter...

Page 10: ...tion of recuperator shown shaded in Figure 3 8 with Moist PAK D by Fiberfrax Eclipse part 57325 DO NOT INSULATE THE BURNER The use of flexible nipples in hot air piping is strongly recommended to acco...

Page 11: ...rectly oriented relative to the gas or air flow Prepare for Adjustment After installation of the burner system components are complete the following steps should be followed in order to prepare for ad...

Page 12: ...tasheet for your particular burner to find the air pressure differential that you need at high fire This is now your target value for high fire NOTE A pressure tap is open when the screw inside the ta...

Page 13: ...m to low fire 2 Choose one burner in the zone Connect the manometer to tap A and tap B of the burner across the air orifice 3 Adjust the automatic zone air control valve until the low fire air pressur...

Page 14: ...l the burners have ignited then drive the zone air butterfly valve to high fire Make sure that the burners stay ignited Step 6 Set High Fire Gas 1 Use the gas curves on the appropriate datasheet to fi...

Page 15: ...spark rod or the ignition wire when the ignition is on You will get a shock Manual Ignition 1 Make sure the gas cock at each burner is closed 2 Start air blower 3 Drive the automatic zone air control...

Page 16: ...els in the exhaust every month If there is any change find the cause and correct it 7 View down the peepsights on the burners and down the exhaust legs of the tubes to check for unusual flame or carbo...

Page 17: ...wiring to the valve Check output from the flame safeguard Check solenoid valve coil for proper operation Replace if necessary Manual gas valve closed Open the gas valve Manual gas cock not open Open...

Page 18: ...g Check and clean filters spark rod and UV scanner If necessary After this step it is important that you clean the spark rod and UV scanner and make sure that there is no excessive soot on the nozzle...

Page 19: ...lectrical wiring Cannot initiate start sequence Air pressure switch has not made contact Check air pressure switch adjustment Check air filter Check blower rotation Check outlet pressure from blower H...

Page 20: ...er mm inch in 3 94 x 10 2 MJ Nm Btu ft standard 26 86 From To Multiply By kiloPascals kPa millibar mbar 10 meter m millimeter mm 1000 millibar mbar kiloPascals kPa 0 1 millimeter mm meter m 0 001 From...

Page 21: ...i...

Page 22: ...Installation Guide 310 11 14 2014 Eclipse Inc All Rights Reserved...

Reviews: